Programming and Set-Up - Programming the UPS
Bypass Operation | Push | and the cursor keys | or |
|
| Bypass Operation: |
| until the display shows: |
|
|
| OFF | |
| To select Bypass Operation, push | . |
|
| ||
| The UPS will switch to Bypass Operation if the |
| ||||
| bypass mains is within the specified tolerance | Bypass Operation | ||||
| range. The display will show: |
|
|
|
|
The load is now supplied from the bypass mains through the static switch. Bypass mains voltage and output voltage will appear on the display.
To return to Normal Operation, push .
The UPS transfers from one operation mode to another without affecting the load.
Boost Charge | To program the UPS for Boost Charge, press |
and browse through the menu, using
the cursor keys or .
The display shows: | Boost Charge: | |
OFF | ||
|
Choose Boost Charge by selecting .
To deactivate, press .
When the Boost Charge function is selected, the UPS will remain in the Boost Charge operational mode for 8 hours. To change the boost charge operating time, contact APC. (The UPS can be programmed to stay in this mode for up to 24 hrs).
AIS 5000 400V Installation Manual | 63 |