Programming and Set-Up - Programming the UPS
Battery Capacity Test
Make sure the UPS has been in normal operation for at least 8 hours and that the batteries are fully charged before performing this test.
To test the Battery Capacity press and
browse through the menu, using the cursor
keys | or |
| until the display shows: |
| |||
|
|
|
|
(xxx indicates the backup time from the last Battery Capacity test). If this test has not been performed before – or if the test has been aborted, the display shows:
To proceed with the test, press | or | to |
abort. |
|
|
The display shows:
Wait until the display shows:
a short audible alarm will sound.
Press until the display shows:
(xxx represents the actual backup time in minutes)
Press or wait 20 seconds until the display shows:
If a mains failure occurs during a battery capacity test, the test will immediately abort. No test results will be obtained and the display will show:
Battery Capacity Test: xxx
???
Battery Operation Time > ...min
Normal Operation Load Power xx%
Battery Capacity Test: xxx
Normal Operation Load Power xx%
???
AIS 5000 400V Installation Manual | 65 |