Setting stack

In the setting stack, the following parameters are changeable:

 

Parameter

Factory Setting

 

 

 

 

Normal Charge Voltage

272 Vdc

 

 

 

 

Boost Charge Voltage

272 Vdc - no boost required

 

 

 

 

Charge Current Max.

Refer to below table

 

 

 

 

Low Battery Warning

216 Vdc

 

 

 

 

Low Battery Shutdown

204 Vdc

 

 

 

 

Boost Charge Time

8 hours

 

 

 

 

Slew rate 0 – 4

1 Hz

 

 

 

 

Charger ON/OFF

ON

 

 

 

 

Inverter and Bypass ON/OFF

ON

 

 

 

 

Battery Back-up Time

Until a battery capacity test has been

 

 

performed, display will show xxx

 

 

 

 

High Battery Temperature

35oC

 

Auto Battery Monitor

ON

 

 

 

 

Battery Summary Error

OFF

 

 

 

 

Remote Shutdown

OFF

 

 

 

 

Remote Shutdown Polarity

HIGH

 

 

 

 

Remote Shutdown Time

2 minutes

 

 

 

 

 

 

 

Max. Charge Current

 

 

 

 

 

UPS

ADC

 

10 kVA

5

 

 

 

 

20 kVA

10

 

 

 

 

30 kVA

15

 

 

 

 

40 kVA

20

 

 

 

 

60 kVA

30

 

 

 

 

80 kVA

40

 

 

 

 

100 kVA

50

 

 

 

990-2440

AIS 5000 400V Installation Manual

69

Image 75
Contents AIS Page Contents Options Operation Modes Page Symbols used in this manual SafetyDisconnect all sources of AC and DC power User SafetyAbout this manual General InformationReceiving and inspecting the UPS Site RequirementsMoving the equipment to site Fitting the air filter Air FilterAir filter sizes Enclosure dimensions Enclosure dimensions and footprintTop and bottom view of 10-30kVA UPS Top and bottom view of 40-60kVA UPS Top and bottom view of 80-100kVA UPS External connection board Connecting the UPS UPS Feet  Conduit Box  Front of Conduit Box Installing Conduit BoxesInput Conduit Output/Bypass Battery Alarm Conduit Access to Input/Output section Low-voltage section cover Communication Interface, EPO Connecting cables Input/Output -60 kVA Input/Output -100 kVA X090 GroundingCommunication interface Emergency Power Off EPOCOM-PORT Communication interface portsOverview of Communication interface COM Interface10kVA 400V UPS Max. Discharge Current a 46 a Nominal Voltage 240Approvals IEC 62040/EN 50091 Class A, VFI-SS-112 Emergency Power Off EPO YesOptions Max 39.4 a Mains Voltage 400 V 3 Wire + G Nom 19.88 kW 33.79 aVoltage 400 V 3 Wire + N + G Nominal Current 28.9 a 20kVA 400V UPSMax. Discharge Current a 91 a External Connection 20kVA 400V UPS Options Max 59.9 a Mains Voltage 400 V 3 Wire + G Nom 28.35 kW 47.86 aVoltage 400 V 3 Wire + N + G Nominal current 43.3 a 30kVA 400V UPSMax. Discharge Current a 135 a External Connection 30kVA 400V UPS Options Max 77.8 a Mains Voltage 400 V 3 Wire + G Nom 36.9 kW 61.93 aVoltage 400 V 3 Wire + N + G Nominal current 57.7 a 40kVA 400V UPSMax. Discharge Current a 179 External Connection 40kVA 400V UPS Options Max 117 a Mains Voltage 400 V 3 Wire + G Nom 54.42 kW 90.08 aVoltage 400 V 3 Wire + N + G Nominal current 86.6 a 60kVA 400V UPSMax. Discharge Current a 266 External Connection 60kVA 400V UPS Options Max 152.8 a Mains Voltage 400 V 3 Wire + G Nom 72.33 kW 118.23 aVoltage 400 V 3 Wire + N + G Nominal current 115.5 a 80kVA 400V UPSMax. Discharge Current a 353 External Connection 80kVA 400V UPS Options 100kVA 400V UPS Max. Discharge Current a 442 External Connection 100kVA 400V UPS Options Options IP32 Drip Shield Mounting the drip shield Drip shield sizes Message Relay BoardMessage Cards and slots Communication CardsDisplay introduction DisplayDisplay functions Display messages Programming the UPS User stackKeys Until the display shows Bypass Operation Push Cursor keys Programming and Set-Up Programming the UPSAuto Boost Charge OFF Battery Capacity Test ??? Battery Monitor Alarm Settings for redundant systems Enter new time HH.MM.SS Setting stack Minutes10 kVA 20 kVA 30 kVA 40 kVA 60 kVA 80 kVA 100 kVA How to change factory settings Operation Modes Operation mode descriptionsNormal to Bypass Operation Bypass to Normal OperationPress Normal to Manual Bypass Operation Load is now supported by the UPS Page 990-2440