Setting stack
In the setting stack, the following parameters are changeable:
| Parameter | Factory Setting |
|
|
|
| Normal Charge Voltage | 272 Vdc |
|
|
|
| Boost Charge Voltage | 272 Vdc - no boost required |
|
|
|
| Charge Current Max. | Refer to below table |
|
|
|
| Low Battery Warning | 216 Vdc |
|
|
|
| Low Battery Shutdown | 204 Vdc |
|
|
|
| Boost Charge Time | 8 hours |
|
|
|
| Slew rate 0 – 4 | 1 Hz |
|
|
|
| Charger ON/OFF | ON |
|
|
|
| Inverter and Bypass ON/OFF | ON |
|
|
|
| Battery | Until a battery capacity test has been |
|
| performed, display will show xxx |
|
|
|
| High Battery Temperature | 35oC |
| Auto Battery Monitor | ON |
|
|
|
| Battery Summary Error | OFF |
|
|
|
| Remote Shutdown | OFF |
|
|
|
| Remote Shutdown Polarity | HIGH |
|
|
|
| Remote Shutdown Time | 2 minutes |
|
|
|
|
|
|
| Max. Charge Current |
|
|
|
|
| UPS | ADC |
| 10 kVA | 5 |
|
|
|
| 20 kVA | 10 |
|
|
|
| 30 kVA | 15 |
|
|
|
| 40 kVA | 20 |
|
|
|
| 60 kVA | 30 |
|
|
|
| 80 kVA | 40 |
|
|
|
| 100 kVA | 50 |
|
|
|
AIS 5000 400V Installation Manual | 69 |