American Power Conversion AIS 5000 manual Nominal Voltage 240, Max. Discharge Current a 442

Page 55

 

 

External Connection - 100kVA 400V UPS

Electrical Output

 

 

 

 

 

 

 

 

Frequency Regulation

50 Hz, + 0.1% free running

Output Voltage Range

100% static symmetrical load + 1%, 100% static asymmetrical load

 

+ 3%,no load to full load + 4%

Output Harmonic Distortion

<3% linear load <5%

Load Crest Factor

5: 1

 

 

Load Power Factor

0.9 leading to 0.7 lagging

Overload Capacity

150% for 1 min., 125% for 10 min., Bypass Operation 1000% for 5

 

cycles

Connection Type

3 PH + N + G

 

 

 

 

Battery - External Only

 

 

 

 

 

 

 

 

 

 

Nominal Voltage

240

V

(Nominal battery voltage assumed to be 2.0 V/cell

 

 

 

(lead technology)

 

 

 

Number of Battery Cells

120

 

 

Float Charge Voltage

272

Volt DC programmable

Charge Voltage Range

100 to 115% of the DC nominal Voltage, + 1% IU characteristic

Low Battery Warning Range

210

- 222 Vdc (Factory Setting 210 V)

Low Battery Shutdown

204

Vdc

Full Load (P)

87.4 kW

(The battery power takes in to account the DC-AC

 

 

 

efficiency of the main inverter for linear load)

 

 

 

Recommended Breaker Size [A]

500

A

Connection Type

Hard Wire 3-wire (DC+/- + G)

Nominal Discharge Current [A]

364

A

(The battery nominal discharge current is based on

 

 

 

the nominal cell Voltage of 2.0 V/cell - number

 

 

 

of cells = 120 which gives a total Voltage of 240V)

 

 

 

Max. Discharge Current [A]

442

A

(The battery max. discharge current is based on a cell

 

 

 

end Voltage of 1.70V/cell which gives a total Voltage

 

 

 

of 204V)

 

 

 

 

 

 

 

Communication and Management

 

 

 

 

 

 

 

 

Control Panel

Multi-function LCD status and control console

RS232 Port

Yes

 

 

Network Management Card 10/100

Yes

 

 

Base T

 

 

 

Audible Alarm

Audible and visible alarms prioritized by severity

Slots Empty

1

 

 

Modbus/BMS Card

Optional

 

 

 

 

990-2440

AIS 5000 400V Installation Manual

49

Image 55
Contents AIS Page Contents Options Operation Modes Page Symbols used in this manual SafetyDisconnect all sources of AC and DC power User SafetyAbout this manual General InformationReceiving and inspecting the UPS Site RequirementsMoving the equipment to site Fitting the air filter Air FilterAir filter sizes Enclosure dimensions Enclosure dimensions and footprintTop and bottom view of 10-30kVA UPS Top and bottom view of 40-60kVA UPS Top and bottom view of 80-100kVA UPS External connection board Connecting the UPS UPS Feet  Conduit Box  Front of Conduit Box Installing Conduit BoxesInput Conduit Output/Bypass Battery Alarm Conduit Access to Input/Output section Low-voltage section cover Communication Interface, EPO Connecting cables Input/Output -60 kVA Input/Output -100 kVA X090 GroundingCommunication interface Emergency Power Off EPOCOM-PORT Communication interface portsOverview of Communication interface COM Interface10kVA 400V UPS Max. Discharge Current a 46 a Nominal Voltage 240Approvals IEC 62040/EN 50091 Class A, VFI-SS-112 Emergency Power Off EPO YesOptions Max 39.4 a Mains Voltage 400 V 3 Wire + G Nom 19.88 kW 33.79 aVoltage 400 V 3 Wire + N + G Nominal Current 28.9 a 20kVA 400V UPSMax. Discharge Current a 91 a External Connection 20kVA 400V UPS Options Max 59.9 a Mains Voltage 400 V 3 Wire + G Nom 28.35 kW 47.86 aVoltage 400 V 3 Wire + N + G Nominal current 43.3 a 30kVA 400V UPSMax. Discharge Current a 135 a External Connection 30kVA 400V UPS Options Max 77.8 a Mains Voltage 400 V 3 Wire + G Nom 36.9 kW 61.93 aVoltage 400 V 3 Wire + N + G Nominal current 57.7 a 40kVA 400V UPSMax. Discharge Current a 179 External Connection 40kVA 400V UPS Options Max 117 a Mains Voltage 400 V 3 Wire + G Nom 54.42 kW 90.08 aVoltage 400 V 3 Wire + N + G Nominal current 86.6 a 60kVA 400V UPSMax. Discharge Current a 266 External Connection 60kVA 400V UPS Options Max 152.8 a Mains Voltage 400 V 3 Wire + G Nom 72.33 kW 118.23 aVoltage 400 V 3 Wire + N + G Nominal current 115.5 a 80kVA 400V UPSMax. Discharge Current a 353 External Connection 80kVA 400V UPS Options 100kVA 400V UPS Max. Discharge Current a 442 External Connection 100kVA 400V UPS Options Options IP32 Drip Shield Mounting the drip shield Drip shield sizes Message Relay BoardMessage Cards and slots Communication CardsDisplay introduction DisplayDisplay functions Display messages User stack Programming the UPSKeys Until the display shows Bypass Operation Push Cursor keys Programming and Set-Up Programming the UPSAuto Boost Charge OFF Battery Capacity Test ??? Battery Monitor Alarm Settings for redundant systems Enter new time HH.MM.SS Minutes Setting stack10 kVA 20 kVA 30 kVA 40 kVA 60 kVA 80 kVA 100 kVA How to change factory settings Operation Modes Operation mode descriptionsBypass to Normal Operation Normal to Bypass OperationPress Normal to Manual Bypass Operation Load is now supported by the UPS Page 990-2440