100kVA 400V UPS
IS100KH
Performance - Linear Load
DC to AC Efficiency [%] | 90.7 |
AC to AC Efficiency [%] | 87.5 |
Heat Dissipation [BTU/h] [W] | 38,745/11,345 |
|
|
Electrical Input |
|
|
|
|
|
Mains |
|
Voltage | 400 V 3 Wire + G |
P Nom. | 90.67 kW |
I Nom. | 146.38 A |
(Nominal input current based on nominal mains |
|
voltage and batteries fully charged at 100% ohmic |
|
load) |
|
I Max. | 193.9 A |
(Maximum input current based on full battery |
|
recharge and nominal mains voltage at 100% ohmic |
|
load) |
|
200 A | |
(Based on continuous full load) |
|
Input Voltage Range | + 10%, |
Input Frequency | 50 Hz + 6% programmable |
Current Distortion | < 12% |
Power Factor | 0.8 - 0.9 |
Bypass |
|
Voltage | 400 V 3 Wire + N + G |
I Nom | 144.3 A |
160 A | |
(Based on continuous full load) |
|
Bypass Voltage Range | + 10% programmable |
|
|
Electrical Output |
|
|
|
|
|
Voltage | 400 V 3 Wire + N + G |
Nominal current | 144.3 A |
(The output current is based on the nominal apparent |
|
power of the UPS) |
|
Frequency Range | 50Hz (0.25, 0.50, |
|
|
48 | AIS 5000 400V Installation Manual |