APC MW II manual External disconnection switches, Input/Output wiring precautions

Page 10

External disconnection switches

Warning: The UPS has no built-in disconnect devices to switch off external AC (Q1 and Q5) and DC (Q7 and Q8) input power. Ensure that the disconnect devices are available as separate components for this installation.

Note: The installer must provide each external disconnect device for this UPS system with

labels displaying the following text: “Isolate the Uninterruptible Power Supply (UPS) as instructed in the User Guide before working on the circuit.”

Input/Output wiring precautions

Warning: Only personnel trained in the construction and operation of the equipment, and the electrical and mechanical hazards involved, must install or remove system components.

Warning: Before you start the installation, verify that all AC and DC power source breakers are in the open position.

Warning: Supply the UPS from a 3 × 400/230 V, L1, L2, L3, N, PE source or a high- impedance grounded system.

Caution: All wiring to be in accordance with applicable national and/or local electrical wiring rules.

Note: Use only copper conductors.

6

Symmetra MW II 1200 kW 3 x 400/230 V Installation - 990-1979E-001

Image 10
Contents Installation Page Contents Specifications Symbols used in this guide Installation safetyPage Inverter Section UPS SectionsSerial number Control/Input/Output SectionExternal Bypass Static Switch Power wiring UPS Wiring PrincipleOverview External disconnection switches Input/Output wiring precautions  AC and PE cable connectionsBattery cables connection Hole distance AC BAT1 + BAT2 External Bypass Static Switch Wiring Top cable entry Maintenance Bypass Panel Communication cable overviewLocation of relay boards Relay BoardsCommunication cables with optional Relay Board Relay Function Mode Special Comments Relay board 1 connectionsRelay board 2 connections Page Electrical Specifications Low-Impedance/High-Impedance EarthingAC Input DC InputAC Input External Bypass SSW AC OutputHeat dissipation Torque specifications Required Breaker Settings 400 V SystemsInput and upstream breakers Output and downstream breakers Dual Mains Installation TN Systems CharacteristicsSystem and Protective Earthing Reference to IEC 60364-4-41Additional requirements for generating sets IEC 60364-5-55 Protective devices in TN systemsTT Systems Protective devices in TT systemsIT Systems Condition Protective devices in IT systemsSee IEC Legal in DK specialcases Symmetra MW Switchgear Service Entrance Earthing arrangements and protective conductors Grounding Page Page 990-1979E-001 2009