APC MW II manual System and Protective Earthing, TN Systems, Characteristics

Page 27

Appendix

System and Protective Earthing

The purpose of this appendix is to describe the system- and protective earthing principles of the Symmetra® MW.

Caution: All wiring to be in accordance with applicable national and/or local electrical wiring rules.

TN Systems

Characteristics

TN systems have one point connected directly to ground. All exposed conductive parts must be connected to that point by protective conductors.

Depending on the way the neutral and protective conductors are fed, there are three types of TN systems:

TN-S system: a separate protective conductor is used in the system

TN-C-S system: the neutral and protective conductors are combined to one single conductor in a part of the system

TN-C system: the neutral and protective conductors are combined to one single conductor in the whole system

Reference to IEC 60364-4-41 413.1.3

All exposed conductive parts of the installation must be connected to the earthed point of the power system by protective conductors which must be earthed at or near to each relevant transformer or generator.

Exposed conductive parts that are accessible at the same time must be connected to the same earthing system, either individually, in groups or collectively.

Normally the earthed point of the power system is the neutral point. If a neutral point is not available or accessible, a phase conductor must be earthed. The phase conductor must not serve as a PEN conductor.

In fixed installations a single conductor may serve both as a protective conductor and a neutral conductor (PEN conductor).

Reference to IEC 60364-5-54 546.2.3

If from any point in the installation the neutral and protective functions are provided by separate conductors, it is inadmissible to connect these conductors to each other from that point. At the point of separation, separate terminals or bars must be provided for the protective and neutral conductors. The PEN conductor must be connected to the terminal or bar intended for the protective conductor.

Symmetra MW II 1200 kW 3 × 400/230 V Installation - 990-1979E-001

23

Image 27
Contents Installation Page Contents Specifications Installation safety Symbols used in this guidePage Control/Input/Output Section UPS SectionsSerial number Inverter SectionExternal Bypass Static Switch UPS Wiring Principle Power wiringOverview Input/Output wiring precautions External disconnection switchesAC and PE cable connections  Hole distance AC Battery cables connection BAT1 + BAT2 External Bypass Static Switch Wiring Top cable entry Communication cable overview Maintenance Bypass PanelRelay Boards Location of relay boardsCommunication cables with optional Relay Board Relay board 1 connections Relay Function Mode Special CommentsRelay board 2 connections Page Low-Impedance/High-Impedance Earthing Electrical SpecificationsDC Input AC InputAC Output AC Input External Bypass SSWHeat dissipation Required Breaker Settings 400 V Systems Torque specificationsInput and upstream breakers Output and downstream breakers Dual Mains Installation Reference to IEC 60364-4-41 CharacteristicsSystem and Protective Earthing TN SystemsProtective devices in TN systems Additional requirements for generating sets IEC 60364-5-55Protective devices in TT systems TT SystemsIT Systems Protective devices in IT systems ConditionSee IEC Legal in DK specialcases Symmetra MW Switchgear Service Entrance Earthing arrangements and protective conductors Grounding Page Page 2009 990-1979E-001