APC MW II manual Earthing arrangements and protective conductors

Page 36

32

Symmetra MW II 1200 kW 3 × 400/230 V Installation - 990-1979E-001

Service Entrance

Residual current protective device can not be used at this point.

Owing to parallel return path for the fault current

Residual Current Sense

N

With reference to IEC 60364-4-41 § 413.1.4.1

Earthing arrangements and protective conductors

-

Symmetra MWTTininstallation

 

 

 

 

 

See:

 

IEC 60364-4-41

§ 413.1.4

 

 

 

 

 

Switchgear

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Q3

 

 

 

 

( PDU )

 

 

 

 

 

 

 

 

 

 

 

Residual Current Sense

Residual current protective device

 

 

 

 

 

 

 

 

 

 

 

can be used.

Q5

 

 

 

 

 

External SSW-Bypass

 

 

Q6

 

 

 

Bypass - input

 

 

 

 

 

Bypass - output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L1

 

 

 

 

 

L1

 

 

 

 

 

 

L2

 

 

 

 

 

L2

 

 

 

 

 

 

L3

 

 

 

 

 

L3

 

 

 

 

 

 

 

 

 

Main Protective Earthing Terminal

 

 

 

 

 

 

 

 

PE

 

 

 

 

 

PE

Q4

 

 

 

 

 

 

 

 

 

 

 

 

 

PE

 

 

 

 

 

 

SymmetraMW

 

 

 

 

 

Q1

 

 

Mains - input

 

i

Delta

 

 

UPS - output

 

 

 

 

 

 

 

 

Inverter

 

 

 

 

 

 

 

 

 

L1

 

 

i

 

 

L1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L2

 

i

 

 

 

L2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EarthingProtectiveCondu ctor

L3

 

 

 

u

 

L3

 

 

 

 

 

Common-mode filter

 

 

u

 

 

 

 

 

 

 

 

 

 

u

 

 

 

 

 

 

 

 

 

 

 

 

M

 

 

 

 

 

 

 

 

 

 

 

 

Main

 

 

 

 

 

 

 

 

 

 

 

 

inverter

 

 

 

 

 

 

 

 

N

 

 

 

 

 

N

 

 

 

 

 

 

E

 

 

 

 

 

 

 

 

 

 

 

PE

 

 

 

Main Protective Earthing Terminal

 

 

 

 

 

 

 

 

PE

 

 

 

 

 

PE

 

 

 

 

 

 

+

-

+

-

 

 

 

 

 

 

 

 

 

Battery 1

 

 

Battery 2

 

 

 

 

 

 

 

 

 

Battery

 

 

 

 

 

 

 

 

 

Suitable earth electrode: RA x

Ia

< 50V

breaker

 

 

 

 

 

 

 

 

 

With reference to IEC 60364-4-41

§ 413.1.4.2

box Q7

 

 

Q8

 

 

 

 

 

 

 

 

 

PE

 

 

 

 

 

 

 

 

 

 

 

 

Battery

 

 

 

 

 

 

 

 

 

 

 

 

rack

 

 

 

 

 

 

 

 

 

 

 

 

Battery 1

 

Battery 2

 

 

 

 

 

 

 

 

 

PE

 

 

 

 

 

 

 

 

 

Image 36
Contents Installation Page Contents Specifications Symbols used in this guide Installation safetyPage UPS Sections Serial numberInverter Section Control/Input/Output SectionExternal Bypass Static Switch UPS Wiring Principle Power wiringOverview External disconnection switches Input/Output wiring precautions  AC and PE cable connectionsBattery cables connection Hole distance AC BAT1 + BAT2 External Bypass Static Switch Wiring Top cable entry Maintenance Bypass Panel Communication cable overviewRelay Boards Location of relay boardsCommunication cables with optional Relay Board Relay Function Mode Special Comments Relay board 1 connectionsRelay board 2 connections Page Electrical Specifications Low-Impedance/High-Impedance EarthingAC Input DC InputAC Output AC Input External Bypass SSWHeat dissipation Required Breaker Settings 400 V Systems Torque specificationsInput and upstream breakers Output and downstream breakers Dual Mains Installation Characteristics System and Protective EarthingTN Systems Reference to IEC 60364-4-41Additional requirements for generating sets IEC 60364-5-55 Protective devices in TN systemsTT Systems Protective devices in TT systemsIT Systems Condition Protective devices in IT systemsSee IEC Legal in DK specialcases Symmetra MW Switchgear Service Entrance Earthing arrangements and protective conductors Grounding Page Page 990-1979E-001 2009