APC MW II manual Grounding

Page 37

Symmetra MW II 1200 kW 3 × 400/230 V Installation - 990-1979E-001

Earthing arrangements and protective conductors - Symmetra MW in -"ITinstallation"

 

 

 

 

 

See:

 

IEC 60364-4-41

§ 413.1.5

 

 

 

 

 

Switchgear

 

 

 

 

 

 

 

 

 

Service Entrance

 

 

 

 

 

 

 

Q3

 

 

( PDU )

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Residual Current Sense

Residual current protective device

 

 

 

 

 

 

 

 

 

 

 

can be used.

 

 

Q5

 

 

 

 

 

External SSW-Bypass

Q6

 

 

 

 

 

Bypass - input

 

 

 

Bypass - output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L1

 

 

 

L1

 

 

 

 

 

 

 

 

L2

 

 

 

L2

 

 

 

 

 

 

 

 

L3

 

 

 

L3

 

 

 

 

 

 

 

 

Main Protective Earthing Terminal

 

 

 

 

 

 

 

 

 

 

PE

 

 

 

PE

Q4

 

 

 

 

 

 

 

 

 

 

 

 

 

PE

 

 

 

 

 

 

 

 

SymmetraMW

 

 

 

 

 

Q1

 

 

Mains - input

 

i

Delta

UPS - output

 

 

 

 

 

 

 

 

 

 

Inverter

 

 

 

 

 

 

 

 

 

L1

 

 

i

L1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L2

 

i

 

L2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L3

 

 

 

L3

 

 

 

 

 

 

 

 

filter

 

 

u

u

 

 

 

 

 

 

 

 

 

 

 

M

 

 

 

 

 

 

 

 

Common-mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

u

 

 

 

 

 

 

 

 

 

 

 

 

Main

 

 

 

 

 

 

Grounding

 

 

 

 

 

inverter

 

 

 

 

 

 

Z

 

 

 

 

 

 

 

 

 

 

 

impedance

 

 

 

 

 

 

 

 

 

 

Insulation

 

 

 

 

 

 

 

 

 

 

 

 

Monitoring

 

 

 

 

 

 

 

 

 

 

 

 

Device

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

N

 

 

 

N

 

 

 

N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Main Protective Earthing Terminal

 

 

 

 

 

Protective Earthing Conductor

ConductorEarthing

 

PE

 

2Battery

 

PE

 

 

 

Z

Grounding

 

1Battery

 

 

 

 

 

 

 

impedance

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+

-

+

-

 

 

 

 

 

 

( Alternative to earth electrode )

 

 

 

 

 

 

 

 

 

 

Requirement !!

 

 

 

 

 

 

 

 

 

 

 

IEC 60664-4-41

§ 413.1.5.4

 

 

Battery

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

breaker

 

 

 

 

 

 

 

 

 

 

 

 

box Q7

 

 

Q8

 

 

 

 

 

 

Suitable earth electrode: RA x Id

< 50V

 

PE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

With reference to IEC 60364-4-41

§ 413.1.5.3

 

 

 

 

 

 

 

 

 

 

 

Alternative:

 

 

 

 

 

 

 

 

 

 

 

 

The exposed-conductive-parts can be earthed individually or in groups.

 

 

 

 

 

 

 

 

 

 

But special demands are required. See IEC 60364-4-41 § 413.1.5.5 a)

 

 

 

 

 

 

 

 

 

 

 

 

 

Battery

 

 

 

 

 

 

 

 

 

 

 

 

rack

 

 

 

 

 

 

 

 

 

 

 

 

Battery 1

 

Battery 2

 

 

 

 

 

 

 

 

 

PE

 

 

 

 

 

 

 

33

Image 37
Contents Installation Page Contents Specifications Installation safety Symbols used in this guidePage Serial number UPS SectionsInverter Section Control/Input/Output SectionExternal Bypass Static Switch Power wiring UPS Wiring PrincipleOverview Input/Output wiring precautions External disconnection switchesAC and PE cable connections  Hole distance AC Battery cables connection BAT1 + BAT2 External Bypass Static Switch Wiring Top cable entry Communication cable overview Maintenance Bypass PanelLocation of relay boards Relay BoardsCommunication cables with optional Relay Board Relay board 1 connections Relay Function Mode Special CommentsRelay board 2 connections Page Low-Impedance/High-Impedance Earthing Electrical SpecificationsDC Input AC InputAC Input External Bypass SSW AC OutputHeat dissipation Torque specifications Required Breaker Settings 400 V SystemsInput and upstream breakers Output and downstream breakers Dual Mains Installation System and Protective Earthing CharacteristicsTN Systems Reference to IEC 60364-4-41Protective devices in TN systems Additional requirements for generating sets IEC 60364-5-55Protective devices in TT systems TT SystemsIT Systems Protective devices in IT systems ConditionSee IEC Legal in DK specialcases Symmetra MW Switchgear Service Entrance Earthing arrangements and protective conductors Grounding Page Page 2009 990-1979E-001