APC MW II manual Low-Impedance/High-Impedance Earthing, Electrical Specifications

Page 21

Specifications

Low-Impedance/High-Impedance Earthing

The Symmetra® MW is easily integrated into either a solid grounded system, or a high-impedance grounded system.

In a solid grounded system, the neutral power source (mains, generator, or UPS) is solidly grounded. In the event of a down-stream ground fault, the fault current will have a path back to the source, and the over-current device feeding the faulted part of the installation will trip and isolate the fault.

In a high-impedance grounded system, the source is grounded with an impedance (grounding resistor). In the event of a down-stream fault, the fault current will be limited by the impedance of the grounding resistor. The value of a high-impedance system is its ability to maintain operation with a given system fault to ground, i.e. the over-current device will only trip at line-to-line faults or double ground faults.

For a high-impedance system to provide enhanced power system reliability and availability, a ground- fault monitoring/alarm system is required.

Note: Grounding electrode conductor to be supplied by the customer.

For more information refer to “Appendix” in Installation Guide.

Electrical Specifications

Warning: Supply the UPS from a dedicated, 3 × 400/230 V, L1, L2, L3, N, PE source or a high-impedance grounded system.

Caution: Ensure clockwise phase rotation (L1, L2, L3) of input voltages.

Caution: AC and DC disconnect switches and overcurent protection must be included in the installation.

Note: All wiring must comply with all applicable national and/or local electrical codes.

Note: Max. prospective RMS short-circuit current on input terminals: 200 kA

Max. prospective RMS short-circuit current on DC terminals: 50 kA

Symmetra MW II 1200 kW 3 x 400/230 V Installation - 990-1979E-001

17

Image 21
Contents Installation Page Contents Specifications Installation safety Symbols used in this guidePage Serial number UPS SectionsInverter Section Control/Input/Output SectionExternal Bypass Static Switch UPS Wiring Principle Power wiringOverview Input/Output wiring precautions External disconnection switchesAC and PE cable connections  Hole distance AC Battery cables connection BAT1 + BAT2 External Bypass Static Switch Wiring Top cable entry Communication cable overview Maintenance Bypass PanelRelay Boards Location of relay boardsCommunication cables with optional Relay Board Relay board 1 connections Relay Function Mode Special CommentsRelay board 2 connections Page Low-Impedance/High-Impedance Earthing Electrical SpecificationsDC Input AC InputAC Output AC Input External Bypass SSWHeat dissipation Required Breaker Settings 400 V Systems Torque specificationsInput and upstream breakers Output and downstream breakers Dual Mains Installation System and Protective Earthing CharacteristicsTN Systems Reference to IEC 60364-4-41Protective devices in TN systems Additional requirements for generating sets IEC 60364-5-55Protective devices in TT systems TT SystemsIT Systems Protective devices in IT systems ConditionSee IEC Legal in DK specialcases Symmetra MW Switchgear Service Entrance Earthing arrangements and protective conductors Grounding Page Page 2009 990-1979E-001