AC Output
AC Output
Voltage | 380 V |
Current Nom (note 8) | 1641 A |
Max (note 7) | 2051 A |
Voltage | 400 V |
Current Nom | 1732 A |
Max (note 7) | 2165 A |
Voltage | 415 V |
Current Nom | 1669 A |
Max (note 7) | 2087 A |
|
|
AC Input External Bypass SSW
The External Bypass SSW is designed to accommodate a continuous overload of 25%.
AC Input External Bypass SSW
External Bypass SSW Max Input Current (100% load) |
|
380 V | 1641 A |
400 V | 1732 A |
415 V | 1669 A |
|
|
Heat dissipation
37.1 kW / 126.7 kBTU/hr (note 6).
Notes
1.Nominal (Nom): Input current based on rated load, nominal input voltage and fully charged batteries.
2.Current limitation is maximum allowed via electronic current limiting and is based on full battery recharge + nominal load and
3.Nominal battery voltage assumed to be 2.0 volts/cell (lead technology).
4.Nominal Battery Discharge current based on rated load, and nominal Battery voltage.
5.Maximum Battery Discharge current based on rated load at end of Discharge.
6.Heat dissipation calculated at rated load capacity.
7.This current is at 125% of rated load and is electronically
8.At 380 V, nominal output is reduced from 200 kW to 180 kW in each section.
Symmetra MW II 1200 kW 3 x 400/230 V Installation - | 19 |