APC MW II manual Battery cables connection, Hole distance AC

Page 12

1.With the top covers removed, drill holes for AC, PE and Battery grommets in areas shown.

2.Re-fit the covers and install the grommets.

3.Feed AC and PE cables through grommets in the Control/Input/Output Section.

Hole distance DC

 

Cable lug

Busbar

44.45 mm

44.45 mm

35.8 mm

fl 13

 

Hole distance AC

 

Cable lug

Busbar

44.45 mm

44.45 mm

58 mm

fl 13

 

Hole distance grounding

 

Cable lug

Busbar

44.45 mm

44.45 mm

46.99 mm

M10 stud

4.Connect PE cable.

5.Connect AC IN cables to normal power and bypass power.

6.Connect AC OUT cables.

Battery cables connection

Warning: Make sure that the battery breakers are open (OFF) prior to running the cables.

Caution: For battery installation and maintenance instructions, refer to the battery manufacturer’s installation manual.

Caution: Over-current protection for the battery circuit is required by code. The minimum DC voltage rating of the battery supply over-current protection device is 500 V.

Note: Over-current protection for the battery circuit is required by national wiring rules.

8

Symmetra MW II 1200 kW 3 x 400/230 V Installation - 990-1979E-001

Image 12
Contents Installation Page Contents Specifications Symbols used in this guide Installation safetyPage UPS Sections Serial numberInverter Section Control/Input/Output SectionExternal Bypass Static Switch UPS Wiring Principle Power wiringOverview External disconnection switches Input/Output wiring precautions  AC and PE cable connectionsBattery cables connection Hole distance AC BAT1 + BAT2 External Bypass Static Switch Wiring Top cable entry Maintenance Bypass Panel Communication cable overviewRelay Boards Location of relay boardsCommunication cables with optional Relay Board Relay Function Mode Special Comments Relay board 1 connectionsRelay board 2 connections Page Electrical Specifications Low-Impedance/High-Impedance EarthingAC Input DC InputAC Output AC Input External Bypass SSWHeat dissipation Required Breaker Settings 400 V Systems Torque specificationsInput and upstream breakers Output and downstream breakers Dual Mains Installation Characteristics System and Protective EarthingTN Systems Reference to IEC 60364-4-41Additional requirements for generating sets IEC 60364-5-55 Protective devices in TN systemsTT Systems Protective devices in TT systemsIT Systems Condition Protective devices in IT systemsSee IEC Legal in DK specialcases Symmetra MW Switchgear Service Entrance Earthing arrangements and protective conductors Grounding Page Page 990-1979E-001 2009