APC MW II manual Legal in DK specialcases

Page 33

Symmetra MW II 1200 kW 3 × 400/230 V Installation - 990-1979E-001

Earthing arrangements and protective conductors - Symmetra MW in "TNSinstallation"-

( Legal in DK - specialcases )

 

 

See:

IEC 60364-4-41 § 413.1.4 and "Stærkstrømsbekendtgørelsen"

§ 551.6.3, Note

 

 

 

 

Switchgear

 

 

 

 

 

 

 

 

 

 

 

 

Service Entrance

 

 

 

 

 

 

 

Q3

 

 

 

 

( PDU )

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Residual current protective

 

 

 

 

 

 

 

 

 

 

 

 

Residual Current Sense

device can be used.

 

Q5

 

 

 

 

 

External SSW-Bypass

 

 

Q6

 

 

 

 

Bypass - input

 

 

 

 

Bypass - output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L1

 

 

 

 

 

L1

 

 

 

 

 

 

 

L2

 

 

 

 

 

L2

 

 

 

 

 

 

 

L3

 

 

 

 

 

L3

 

 

 

 

 

 

 

 

 

 

Main Protective Earthing Terminal

 

 

 

 

 

 

 

 

 

PE

 

 

 

 

 

PE

Q4

 

 

Residual current protective device can not be

 

 

 

 

 

 

 

 

 

 

 

PE

 

 

 

 

 

 

 

 

 

 

 

 

 

used at this point.

 

 

 

 

 

 

 

 

 

 

 

 

 

Owing to parallel return path for the fault current

 

 

 

 

 

 

 

 

 

 

 

 

 

Sense

 

 

 

 

 

 

SymmetraMW

 

 

 

 

 

Q1

 

 

 

 

i

Inverter

 

UPS - output

 

 

 

Current

 

 

Mains - input

 

 

Delta

 

 

 

 

 

 

 

L2

 

 

 

 

 

L2

 

 

 

 

 

 

 

L1

 

 

i

 

 

L1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Residual

 

 

EarthingProtectiveConductor

mode-Commonfilter

 

i

 

 

 

 

 

 

 

 

 

 

 

 

u

 

L3

 

 

 

 

 

 

 

L3

 

 

 

u

 

 

 

 

 

 

 

 

 

 

 

u

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M

 

 

 

 

 

 

 

 

 

 

 

 

 

Main

 

 

 

 

 

 

 

 

 

 

 

 

 

inverter

 

 

 

 

 

 

 

 

 

N

 

 

 

 

 

N

 

 

 

N

 

 

 

 

 

 

 

 

 

 

 

 

 

PE

 

 

 

E

 

 

 

 

 

 

 

 

 

 

Protective Earthing Conductor

 

 

 

 

Main Protective Earthing Terminal

 

 

 

 

 

 

 

 

 

PE

 

 

 

 

 

PE

 

 

 

 

 

 

 

+

-

+

-

 

 

 

 

 

 

 

 

 

 

Battery 1

 

 

Battery 2

 

 

 

 

 

 

With reference to:

Legal in DK ( Special cases )

 

 

Battery

 

 

 

 

 

 

 

 

 

IEC 60364-4-41 § 413.1.3.1

With reference to:

 

 

breaker

 

 

 

 

 

 

 

 

 

 

 

 

box Q7

 

 

Q8

 

 

 

 

 

 

Minimum cross-sectional areas:

Stærkstrømsbekendtgørelsen

§ 551.6.3 Note

 

 

 

 

 

 

 

 

 

IEC 364-5-54 § 543.1.1

( § 551.6.3 is missing in IEC 60364-5-55 )

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PE

 

 

 

 

 

 

 

 

 

 

 

 

 

Battery

 

 

 

 

 

 

 

 

 

 

 

 

 

rack

 

 

 

 

 

 

 

 

 

 

 

 

 

Battery 1

 

Battery 2

 

 

 

 

 

 

 

 

 

 

PE

 

 

 

 

 

 

 

 

 

29

Image 33
Contents Installation Page Contents Specifications Installation safety Symbols used in this guidePage Serial number UPS SectionsInverter Section Control/Input/Output SectionExternal Bypass Static Switch UPS Wiring Principle Power wiringOverview Input/Output wiring precautions External disconnection switchesAC and PE cable connections  Hole distance AC Battery cables connection BAT1 + BAT2 External Bypass Static Switch Wiring Top cable entry Communication cable overview Maintenance Bypass PanelRelay Boards Location of relay boardsCommunication cables with optional Relay Board Relay board 1 connections Relay Function Mode Special CommentsRelay board 2 connections Page Low-Impedance/High-Impedance Earthing Electrical SpecificationsDC Input AC InputAC Output AC Input External Bypass SSWHeat dissipation Required Breaker Settings 400 V Systems Torque specificationsInput and upstream breakers Output and downstream breakers Dual Mains Installation System and Protective Earthing CharacteristicsTN Systems Reference to IEC 60364-4-41Protective devices in TN systems Additional requirements for generating sets IEC 60364-5-55Protective devices in TT systems TT SystemsIT Systems Protective devices in IT systems ConditionSee IEC Legal in DK specialcases Symmetra MW Switchgear Service Entrance Earthing arrangements and protective conductors Grounding Page Page 2009 990-1979E-001