APC MW II manual Symmetra MW

Page 34

30

Earthing arrangements and protective conductors - Symmetra MW in "TN-installation"C-S

Symmetra MW II

Service Entrance

Residual current protective device can not be used.

Switchgear

Q5

See:

IEC 60364-4-41

§ 413.1.3

 

 

 

 

Q3

 

 

 

( PDU )

 

 

 

 

 

Residual current protective

 

 

 

 

Current Sense

device can be used.

 

 

 

 

 

External SSW-Bypass

 

Residual

 

Bypass - input

 

Bypass - output

Q6

 

 

 

 

L1

 

L1

 

 

 

L2

 

L2

 

 

 

L3

 

L3

 

 

 

Main Protective Earthing Terminal

 

 

 

 

PE

 

PE

Q4

 

 

 

 

 

 

PE

 

SymmetraMW

 

 

 

 

1200 kW 3 × 400/230 V Installation

PEN

Residual Current Sense

PEN

Q1

ConductorEarthing

Protective

PE

Mains - input

 

i

Delta

 

UPS - output

 

 

Inverter

 

 

L1

 

 

i

 

L1

 

 

 

 

 

L2

 

i

 

 

L2

 

 

 

 

 

L3

 

 

 

 

L3

 

 

 

 

u

u

filter

 

 

 

 

 

 

 

 

M

Common-mode

 

 

 

 

 

 

 

 

Main

 

 

 

 

inverter

 

 

 

 

u

N

 

 

 

 

N

E

 

 

 

 

 

 

 

 

 

Main Protective Earthing Terminal

PE

 

 

 

 

PE

+

-

+

-

 

 

Battery 1

 

 

Battery 2

 

 

- 990-1979E-001

With reference to:

IEC 60364-4-41 § 413.1.3.1

Suitable earth electrode

with reference to IEC 60364-5-55 § 551.4.2

Battery

 

breaker

 

box Q7

Q8

PE

 

Battery

 

rack

 

Battery 1

Battery 2

PE

Image 34
Contents Installation Page Contents Specifications Symbols used in this guide Installation safetyPage Inverter Section UPS SectionsSerial number Control/Input/Output SectionExternal Bypass Static Switch Power wiring UPS Wiring PrincipleOverview External disconnection switches Input/Output wiring precautions  AC and PE cable connectionsBattery cables connection Hole distance AC BAT1 + BAT2 External Bypass Static Switch Wiring Top cable entry Maintenance Bypass Panel Communication cable overviewLocation of relay boards Relay BoardsCommunication cables with optional Relay Board Relay Function Mode Special Comments Relay board 1 connectionsRelay board 2 connections Page Electrical Specifications Low-Impedance/High-Impedance EarthingAC Input DC InputAC Input External Bypass SSW AC OutputHeat dissipation Torque specifications Required Breaker Settings 400 V SystemsInput and upstream breakers Output and downstream breakers Dual Mains Installation TN Systems CharacteristicsSystem and Protective Earthing Reference to IEC 60364-4-41Additional requirements for generating sets IEC 60364-5-55 Protective devices in TN systemsTT Systems Protective devices in TT systemsIT Systems Condition Protective devices in IT systemsSee IEC Legal in DK specialcases Symmetra MW Switchgear Service Entrance Earthing arrangements and protective conductors Grounding Page Page 990-1979E-001 2009