APC MW II manual Switchgear Service Entrance

Page 35

Symmetra MW II 1200 kW 3 × 400/230 V Installation - 990-1979E-001

Earthing arrangements and protective conductors - Symmetra MW inCTNinstallation-

See: IEC 60364-4-41 § 413.1.3

This system configuration is not recommended

Switchgear

 

 

 

 

 

 

 

Service Entrance

 

 

 

 

 

Q3

 

 

 

 

 

 

 

 

Q5

 

 

 

External SSW-Bypass

 

Bypass - input

 

 

 

 

Bypass - output

Q6

 

 

 

 

 

 

L1

 

 

 

 

L1

 

 

L2

 

 

 

 

L2

 

 

L3

 

 

 

 

L3

 

 

Main Protective Earthing Terminal

 

 

 

 

PE

 

 

 

 

PE

Q4

 

 

 

 

 

 

 

 

 

 

 

 

SymmetraMW

 

Q1

Mains - input

 

i

Delta

 

UPS - output

 

 

 

 

Inverter

 

 

 

 

L1

 

 

i

 

L1

 

 

 

 

 

 

 

 

 

L2

 

i

 

 

L2

 

 

 

 

 

 

 

 

 

L3

 

 

 

 

L3

 

 

 

 

 

 

u

u

 

 

filter

 

 

 

 

M

 

 

Common-mode

 

 

 

 

 

 

 

 

 

 

u

 

 

 

 

 

 

 

Main

 

 

 

 

 

 

 

inverter

 

 

N

 

 

 

 

N

 

PEN

E

 

 

 

 

 

 

PEN

 

 

 

 

 

 

 

PEN

 

 

 

Main Protective Earthing Terminal

PEN

 

PE

 

 

 

 

PE

 

 

+

-

+

-

 

 

 

 

1

 

 

2

 

 

 

 

Battery

 

 

Battery

 

The "Common-Mode Filter" has no effect in this

 

 

 

 

 

 

 

system configuration.

 

With reference to:

 

 

 

IEC 60364-4-41 § 413.1.3.1

Suitable earth electrode

Battery

 

 

with reference to IEC 60364-5-55 § 551.4.2

 

 

 

breaker

 

 

 

box Q7

Q8

 

 

PE

 

 

 

Battery

 

 

 

rack

 

 

 

Battery 1

Battery 2

 

 

PE

 

( PDU )

N

PEN

PE

31

Image 35
Contents Installation Page Contents Specifications Installation safety Symbols used in this guidePage Control/Input/Output Section UPS SectionsSerial number Inverter SectionExternal Bypass Static Switch Overview UPS Wiring PrinciplePower wiring Input/Output wiring precautions External disconnection switchesAC and PE cable connections  Hole distance AC Battery cables connection BAT1 + BAT2 External Bypass Static Switch Wiring Top cable entry Communication cable overview Maintenance Bypass PanelCommunication cables with optional Relay Board Relay BoardsLocation of relay boards Relay board 1 connections Relay Function Mode Special CommentsRelay board 2 connections Page Low-Impedance/High-Impedance Earthing Electrical SpecificationsDC Input AC InputHeat dissipation AC OutputAC Input External Bypass SSW Input and upstream breakers Required Breaker Settings 400 V SystemsTorque specifications Output and downstream breakers Dual Mains Installation Reference to IEC 60364-4-41 CharacteristicsSystem and Protective Earthing TN SystemsProtective devices in TN systems Additional requirements for generating sets IEC 60364-5-55Protective devices in TT systems TT SystemsIT Systems Protective devices in IT systems ConditionSee IEC Legal in DK specialcases Symmetra MW Switchgear Service Entrance Earthing arrangements and protective conductors Grounding Page Page 2009 990-1979E-001