APC MW II manual Additional requirements for generating sets IEC 60364-5-55

Page 28

If there are other effective earth connections, the protective conductors must be connected to such points when it is possible. It may be necessary to earth at additional points to ensure that the potentials of protective conductors remain as close as possible to that of earth in case of a fault.

Additional requirements for generating sets (IEC 60364-5-55 551.4.2)

To be used when the generating set provides a switched alternative to the public supply.

Protection by automatic disconnection of supply must not rely on the connection to the earthed points of the public supply system when the generator is operating as a switched alternative to a TN system. A suitable earth electrode must be provided.

Protective devices in TN systems

The following protective devices are recognized in TN systems:

Overcurrent protective devices

Residual current protective devices (not to be used in TN-C systems)

When a residual current protective device is used in a TN-C-S system, a PEN conductor must not be used on the load side. The connection of the protective conductor to the PEN conductor must be made on the source side of the residual current protective device (see below illustration):

L1

SOURCE L1 L1

PEN

 

ResidualCurrent Sense

 

 

 

L1

 

 

 

 

 

 

L1

LOAD

 

 

 

 

L1

 

 

 

 

 

 

 

 

N

 

 

 

 

 

 

PE

 

 

 

 

The characteristics of protective devices and the circuit impedances shall be such that, if a fault of negligible impedance occurs anywhere in the installation between a phase conductor and a protective conductor or exposed conductive part, automatic disconnection of the supply will occur within 5 seconds (valid for distribution circuits), the following condition fulfilling this requirement:

Zs Ia U0

In the condition:

Zs

is the impedance of the fault loop comprising the source, the live conductor up to the point of the

 

fault, and the protective conductor between the point of the fault and the source

Ia

is the current causing the automatic operation of the disconnecting protective device within a

 

conventional time not exceeding five seconds

U0

is the nominal AC RMS voltage to earth

24

Symmetra MW II 1200 kW 3 × 400/230 V Installation - 990-1979E-001

Image 28
Contents Installation Page Contents Specifications Symbols used in this guide Installation safetyPage UPS Sections Serial numberInverter Section Control/Input/Output SectionExternal Bypass Static Switch Power wiring UPS Wiring PrincipleOverview External disconnection switches Input/Output wiring precautions  AC and PE cable connectionsBattery cables connection Hole distance AC BAT1 + BAT2 External Bypass Static Switch Wiring Top cable entry Maintenance Bypass Panel Communication cable overviewLocation of relay boards Relay BoardsCommunication cables with optional Relay Board Relay Function Mode Special Comments Relay board 1 connectionsRelay board 2 connections Page Electrical Specifications Low-Impedance/High-Impedance EarthingAC Input DC InputAC Input External Bypass SSW AC OutputHeat dissipation Torque specifications Required Breaker Settings 400 V SystemsInput and upstream breakers Output and downstream breakers Dual Mains Installation Characteristics System and Protective EarthingTN Systems Reference to IEC 60364-4-41Additional requirements for generating sets IEC 60364-5-55 Protective devices in TN systemsTT Systems Protective devices in TT systemsIT Systems Condition Protective devices in IT systemsSee IEC Legal in DK specialcases Symmetra MW Switchgear Service Entrance Earthing arrangements and protective conductors Grounding Page Page 990-1979E-001 2009