Technical Specifications
9.0TECHNICAL SPECIFICATIONS
9.1Conformity and Standards
The UPS has been designed to conform to the following European and international standards:
Table 29 Compliance with European, international standards
| Description | Normative reference | |
| 
 | 
 | |
| General and safety requirements for UPS used in | EN  | |
| operator access areas | ||
| 
 | ||
| Electromagnetic compatibility (EMC) requirements for | EN  | |
| UPS | ||
| 
 | ||
| Method of specifying the performance and test | EN  | |
| requirements of UPS | ||
| 
 | 
The product standards in Table 29 incorporate relevant compliance clauses with generic IEC and EN standards for safety (IEC/EN/AS60950), electromagnetic emission and immunity (IEC/EN/AS61000 series) and construction (IEC/EN/AS60146 series and 60529).
Table 30 Environmental characteristics
| 
 | Unit of | 
 | 
 | 
 | 
 | 
 | 
 | |
| Rated power, kVA | Measurement | 10 | 
 | 15 | 20 | 
 | 30 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| Acoustic Noise Level at 1 Meter (39 in) | dBa | 51.0 | 
 | 51.5 | 51.6 | 
 | 56 | |
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 
 | 
 | 
 | ≤1000m (3280 ft) above sea level | 
 | ||||
| Altitude of Operation | m (ft) | |||||||
| 
 | 
 | 1000 and 2000 m (3280 and 6560 ft) | 
 | |||||
| Relative Humidity | - | 
 | 
 | 0 to 95% non condensing | 
 | |||
| 
 | 
 | 
 | 
 | 
 | 
 | |||
| 
 | 
 | 
 | 
 | 0 to 40  | 
 | |||
| Operating Temperature | °C (°F) | Battery life is halved for every 10° (18°) increase | ||||||
| 
 | 
 | 
 | 
 | above 20° (68°) | 
 | |||
| °C (°F) | 
 | 
 | 
 | |||||
| 
 | 
 | 
 | 
 | 
 | 
 | |||
| Recommended Battery Storage | °C (°F) | 
 | 
 | 
 | ||||
| Temperature | (20°C [68°F] for optimum battery storage) | |||||||
| 
 | ||||||||
Table 31 Overall efficiency, heat losses and air exchange
| 
 | Unit of | 
 | 
 | 
 | 
 | 
 | 
| Rated Power, kVA | Measurement | 10 | 15 | 
 | 20 | 30 | 
| Normal Mode (dual conversion) | % | 90.4 | 91.2 | 
 | 91.3 | 91.9 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| ECO Mode | % | 93.2 | 94.2 | 
 | 94.7 | 96.6 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| Inverter Efficiency (DC/AC) | 
 | 
 | 
 | 
 | 
 | 
 | 
| (battery at nominal voltage 480VDC and  | 
 | 
 | 
 | 
 | 
 | |
| Rated Power, | kVA | 10 | 15 | 
 | 20 | 30 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| Battery Mode | % | 91.3 | 91.7 | 
 | 92.0 | 92.5 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| Heat Loss & Air Exchange (Ventilation) | 
 | 
 | 
 | 
 | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| Rated Power | kVA | 10 | 15 | 
 | 20 | 30 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| Normal Mode | kW | 1.6 | 1.8 | 
 | 2.2 | 2.6 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| ECO Mode | kW | 1.3 | 1.4 | 
 | 1.4 | 1.5 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| No Load | kW | 1.3 | 1.3 | 
 | 1.3 | 1.3 | 
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| Maximum Forced Air Cooling (front intake, back exhaust) | L/sec (m3/hr) | 119 | 
 | 239 (860) | 
 | |
| 
 | 
 | (428) | 
 | 
 | 
 | 
 | 
| Input and output voltage 400VAC, battery charged, full rated linear load | 
 | 
 | 
 | 
 | 
 | |
73