Technical Specifications
9.0TECHNICAL SPECIFICATIONS
9.1Conformity and Standards
The UPS has been designed to conform to the following European and international standards:
Table 29 Compliance with European, international standards
Description | Normative reference | |
|
| |
General and safety requirements for UPS used in | EN | |
operator access areas | ||
| ||
Electromagnetic compatibility (EMC) requirements for | EN | |
UPS | ||
| ||
Method of specifying the performance and test | EN | |
requirements of UPS | ||
|
The product standards in Table 29 incorporate relevant compliance clauses with generic IEC and EN standards for safety (IEC/EN/AS60950), electromagnetic emission and immunity (IEC/EN/AS61000 series) and construction (IEC/EN/AS60146 series and 60529).
Table 30 Environmental characteristics
| Unit of |
|
|
|
|
|
| |
Rated power, kVA | Measurement | 10 |
| 15 | 20 |
| 30 | |
|
|
|
|
|
|
|
| |
Acoustic Noise Level at 1 Meter (39 in) | dBa | 51.0 |
| 51.5 | 51.6 |
| 56 | |
|
|
|
|
|
|
|
| |
|
|
| ≤1000m (3280 ft) above sea level |
| ||||
Altitude of Operation | m (ft) | |||||||
|
| 1000 and 2000 m (3280 and 6560 ft) |
| |||||
Relative Humidity | - |
|
| 0 to 95% non condensing |
| |||
|
|
|
|
|
| |||
|
|
|
| 0 to 40 |
| |||
Operating Temperature | °C (°F) | Battery life is halved for every 10° (18°) increase | ||||||
|
|
|
| above 20° (68°) |
| |||
°C (°F) |
|
|
| |||||
|
|
|
|
|
| |||
Recommended Battery Storage | °C (°F) |
|
|
| ||||
Temperature | (20°C [68°F] for optimum battery storage) | |||||||
|
Table 31 Overall efficiency, heat losses and air exchange
| Unit of |
|
|
|
|
|
Rated Power, kVA | Measurement | 10 | 15 |
| 20 | 30 |
Normal Mode (dual conversion) | % | 90.4 | 91.2 |
| 91.3 | 91.9 |
|
|
|
|
|
|
|
ECO Mode | % | 93.2 | 94.2 |
| 94.7 | 96.6 |
|
|
|
|
|
|
|
Inverter Efficiency (DC/AC) |
|
|
|
|
|
|
(battery at nominal voltage 480VDC and |
|
|
|
|
| |
Rated Power, | kVA | 10 | 15 |
| 20 | 30 |
|
|
|
|
|
|
|
Battery Mode | % | 91.3 | 91.7 |
| 92.0 | 92.5 |
|
|
|
|
|
|
|
Heat Loss & Air Exchange (Ventilation) |
|
|
|
|
|
|
|
|
|
|
|
|
|
Rated Power | kVA | 10 | 15 |
| 20 | 30 |
|
|
|
|
|
|
|
Normal Mode | kW | 1.6 | 1.8 |
| 2.2 | 2.6 |
|
|
|
|
|
|
|
ECO Mode | kW | 1.3 | 1.4 |
| 1.4 | 1.5 |
|
|
|
|
|
|
|
No Load | kW | 1.3 | 1.3 |
| 1.3 | 1.3 |
|
|
|
|
|
|
|
Maximum Forced Air Cooling (front intake, back exhaust) | L/sec (m3/hr) | 119 |
| 239 (860) |
| |
|
| (428) |
|
|
|
|
Input and output voltage 400VAC, battery charged, full rated linear load |
|
|
|
|
|