Technical Specifications

Table 36 Bypass mains input

Rated power, kVA

Unit of

10

 

15

 

20

 

30

Measurement

 

 

 

 

 

 

 

 

 

 

 

Rated AC Voltage 1

 

 

 

 

380/400/415 V

 

VAC

three-phase four-wire, sharing neutral with the rectifier input

 

 

 

and providing neutral reference to the output

 

Rated Current

 

 

 

 

 

 

 

 

380V

A

15

 

23

 

30

 

45

400V

A

15

 

22

 

29

 

43

415V

A

14

 

21

 

28

 

42

 

 

 

 

135% long term

 

Overload Capacity

%

 

 

 

170% 10 min

 

 

 

 

 

 

1000% 100 ms

 

Upstream Protection,

N/A

 

Thermomagnetic circuit breaker, rated up to 125%

 

Bypass Line (by others)

 

of nominal output current. IEC 60947-2 curve C.

 

 

 

 

Current Rating of Neutral Cable

A

 

 

 

1.7 x In

 

Frequency 2

Hz

 

 

 

50 / 60

 

 

Transfer Time (between

 

 

 

Synchronous transfer: ≤1ms

 

ms

Asynchronous transfer (default): 15 ms (50 Hz), 13.3 ms (60 Hz)

bypass and inverter)

 

 

 

or 40, 60, 80, 100 ms, selectable

 

 

 

 

 

 

 

 

 

Upper limit: +10, +15 or +20, default +15

 

Bypass Voltage Tolerance

% VAC

 

Lower limit –10, -20, -30 or -40, default: -20

 

 

 

(delay time to accept steady bypass voltage: 10 sec)

Bypass Frequency Tolerance

%

 

 

± 2.5 ± 5 ± 10 or ± 20 default ±10

 

Synchronisation - Window

Hz

 

Rated frequency ±2Hz (selectable ± 0.5 to ±3Hz)

 

1.Factory set to 400V – 380 or 415V selectable by commissioning engineer.

2.Factory set to 50Hz; 60 Hz selectable by commissioning engineer. Bypass condition ignored when UPS set as frequency converter.

76

Page 84
Image 84
Liebert NX UPS System user manual Bypass mains input