Technical Specifications
Table 36 Bypass mains input
| Rated power, kVA | Unit of | 10 | 
 | 15 | 
 | 20 | 
 | 30 | |
| Measurement | 
 | 
 | 
 | ||||||
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | ||
| Rated AC Voltage 1 | 
 | 
 | 
 | 
 | 380/400/415 V | 
 | |||
| VAC | |||||||||
| 
 | 
 | 
 | and providing neutral reference to the output | 
 | |||||
| Rated Current | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | |
| 380V | A | 15 | 
 | 23 | 
 | 30 | 
 | 45 | |
| 400V | A | 15 | 
 | 22 | 
 | 29 | 
 | 43 | |
| 415V | A | 14 | 
 | 21 | 
 | 28 | 
 | 42 | |
| 
 | 
 | 
 | 
 | 135% long term | 
 | ||||
| Overload Capacity | % | 
 | 
 | 
 | 170% 10 min | 
 | |||
| 
 | 
 | 
 | 
 | 
 | 1000% 100 ms | 
 | |||
| Upstream Protection, | N/A | 
 | Thermomagnetic circuit breaker, rated up to 125% | 
 | |||||
| Bypass Line (by others) | 
 | of nominal output current. IEC  | 
 | ||||||
| 
 | 
 | 
 | |||||||
| Current Rating of Neutral Cable | A | 
 | 
 | 
 | 1.7 x In | 
 | |||
| Frequency 2 | Hz | 
 | 
 | 
 | 50 / 60 | 
 | 
 | ||
| Transfer Time (between | 
 | 
 | 
 | Synchronous transfer: ≤1ms | 
 | ||||
| ms | Asynchronous transfer (default): 15 ms (50 Hz), 13.3 ms (60 Hz) | ||||||||
| bypass and inverter) | |||||||||
| 
 | 
 | 
 | or 40, 60, 80, 100 ms, selectable | 
 | |||||
| 
 | 
 | 
 | 
 | 
 | |||||
| 
 | 
 | 
 | Upper limit: +10, +15 or +20, default +15 | 
 | |||||
| Bypass Voltage Tolerance | % VAC | 
 | Lower limit  | 
 | |||||
| 
 | 
 | (delay time to accept steady bypass voltage: 10 sec) | |||||||
| Bypass Frequency Tolerance | % | 
 | 
 | ± 2.5 ± 5 ± 10 or ± 20 default ±10 | 
 | ||||
| Synchronisation - Window | Hz | 
 | Rated frequency ±2Hz (selectable ± 0.5 to ±3Hz) | 
 | |||||
1.Factory set to 400V – 380 or 415V selectable by commissioning engineer.
2.Factory set to 50Hz; 60 Hz selectable by commissioning engineer. Bypass condition ignored when UPS set as frequency converter.
76