Single Module UPS Installation

1.8.5Emergency Power Off Input

The UPS has an Emergency Power Off (EPO) function that operates by a button on the control panel or by a remote contact provided by the user. The EPO button is under a hinged, clear plastic shield.

The X2 slot, shown in Figure 5, is the remote EPO input interface. The EPO has an NO/NC contact point that becomes active when shorting terminals X2: 3 and 4 or open terminal connection X2: 2 and 1

If an external emergency stop facility is required, it is connected terminals X2: 1&2 or X2: 3&4 of the auxiliary terminal block (X2). It also is connected to the normally open or normally closed remote stop switch between these two terminals using shielded cable (see Figure 5 and Table 7). If this function is not used, terminals X2: 3&4 must be opened and X2: 1&2 must be closed.

Table 7 EPO input contact relays

Position

Name

Description

J28.1

EPO_NC

EPO activated when opened to J28.2

 

 

 

J28.2

EPO_NC

EPO activated when opened to J28.1

 

 

 

J28.3

EPO_NO

EPO activated when shorted to J28.4

 

 

 

J28.4

EPO_NO

EPO activated when shorted to J28.3

 

 

 

NOTE

The emergency stop action within the UPS shuts down the rectifier, inverter and static bypass. It does not internally disconnect the input power supply. To disconnect ALL power to the UPS, open the upstream feeder breaker(s) when the remote EPO is activated.

NOTE

Normally closed EPO – X2: 1,2, these terminals are supplied factory-linked on the monitor board and must remain installed if using NC contacts.

NOTE

All auxiliary cables of terminal must be double-insulated. Wire should be 0.5-1.5mm2

(16-20AWG) stranded for maximum runs between 25 and 50 meters (82-164ft.) respectively.

X5: Auxiliary DC Power Output

Auxiliary DC power for modem or external SNMP card. The voltage is between 9V to 12V. The maxi- mum current is 500mA.

X6: Analog Input Interface

Two analog signal channels with an input range is from 0 to +12V. The precision of detection is ÷3%.

X6 pin 1: Not used

X6 pin 2: +12V

X6 pin 3: ENV-T – environment temperature detection

X6 pin 4: GND

X7: External Battery Temperature Detector Interface

Interface for TMP12Z temperature detector, normally connected to an external battery cabinet (see Figure 7).

Pin reference:

X7 pin 1: Not used

X7 pin 2: +12V (Power supply for Temperature Monitoring Probe)

X7 pin 3: BAT-T (Battery Temperature signal)

X7 pin 4: GND

15

Page 23
Image 23
Liebert NX UPS System user manual Emergency Power Off Input, X5 Auxiliary DC Power Output, X6 Analog Input Interface