
Single Module UPS Installation
1.8Dry Contacts
The UPS provides input dry contacts and output dry contacts.
1.8.1Input Dry Contacts
There are several input dry contacts at the X3 slot.
Figure 3 Input dry contacts
12V 12V

 12V
 12V
12V
X3
| 
 | J4 | 
 | 
 | 
| 12V | GEN | BtG | ENV | 
| 
 | J26 | 
 | 
 | 
| GND | 12V | AUX I | T IT | 
| 
 | J30 | 
 | 
 | 
| AUX O | T OT | F FAN | FUSE | 
J10
| OL | GND | FB | DRV | 
X3 Ancillary Control and Alarms
X3 IN DRY: Environmental, Battery Ground Fault and Generator Contacts
The UPS accepts external signalling from 
| Table 3 | Input dry contacts at X3 | ||
| 
 | 
 | 
 | 
 | 
| Position | 
 | Name | Description | 
| J4.1 | 
 | ENV3 | Battery Room Alarm (NC) | 
| J4.2 | 
 | BtG | Battery Ground Fault Detection (NC) | 
| J4.3 | 
 | GEN1,2 | On Generator (NO) | 
| J4.4 | 
 | +12V | +12V Power | 
1 - Must be configured by configuration software before becoming active.
2 - When activated, the charger current can be limited, via software, to a percentage of the full charger current 
1.8.2Maintenance Bypass Cabinet Interface
J26 and J30 are the MBC interface.
Table 4 Maintenance bypass cabinet interface
| Position | Name | Description | 
| J26.1 | T_IT1 | Input transformer overtemperature (NC) | 
| J26.2 | AUX_I | Reserved | 
| J26.3 | +12V | +12V Power | 
| J26.4 | GND | Power Ground | 
| J30.1 | FUSE | Reserved | 
| J30.2 | F_FAN | Fan Fail Alarm (NC) | 
| J30.3 | T_OT1 | Output Transformer Overtemperature (NC) | 
| J30.4 | AUX_O | Reserved | 
1- Must be configured by software before becoming active
NOTE
All auxiliary cables of terminal must be 
12
