
Operator Control Panel and Display
| Table 22 | UPS messages (continued) | ||
| 
 | 
 | 
 | |
| Message | 
 | Description / Suggested Action (if any) | |
| 
 | 
 | The UPS is confirmed to overload and the overload times out. | |
| 
 | 
 | Note 1: the highest loaded phase will indicate overload  | |
| 
 | 
 | Note 2: When the timer is active then alarm “unit overload” should also be active as the load is | |
| 
 | 
 | above nominal. | |
| 
 | 
 | Note 3: When the timer has expired, the inverter Static Switch is opened and the load | |
| Unit Over load Timeout | transferred to bypass. The inverter shutdown and will restart after 10 seconds. | ||
| 
 | 
 | Note 4: If the load decreases lower than 95% after 5 minutes, the system will transfer back to | |
| 
 | 
 | inverter mode. | |
| 
 | 
 | Confirm that the alarm is genuine by checking the load percent indicated on the LCD. If an | |
| 
 | 
 | overload is indicated then check the load, and investigate any additional load connected prior to | |
| 
 | 
 | the alarm (if applicable). | |
| Byp. Abnormal Shutdown | Both bypass and inverter voltages unavailable. Load interruption | ||
| 
 | 
 | ||
| Inverter Over Current | Inverter Pulse Width Modulation module overloaded. | ||
| 
 | 
 | 
 | |
| 
 | 
 | The phase sequence direction of bypass voltage is reversed. | |
| 
 | 
 | Normally, the phase of phase B lags 120 degrees behind phase A, and the phase of phase C | |
| Bypass Phase Reversed | lags 120 degrees behind phase B. | ||
| 
 | 
 | Verify that the phase rotation of the bypass supply presented to the UPS is correct, and rectify it | |
| 
 | 
 | if it is found to be in error | |
| Load Impact Transfer | A transfer to bypass occurred due to a large step load. The UPS should recover automatically. | ||
| Turn on connected equipment in sequential order to reduce the step loading of the inverter. | |||
| 
 | 
 | ||
| 
 | 
 | The load is on bypass power due to excessive number of transfers that occurred within the last | |
| Transfer  | hour. | ||
| The UPS will recover automatically and will transfer the load back to inverter power within an | |||
| 
 | 
 | ||
| 
 | 
 | hour. | |
| 
 | 
 | ||
| Load Sharing Fault | UPS modules within a parallel system are not sharing the load current equally. | ||
| 
 | 
 | ||
| DC Bus Abnormal | DC input voltage to inverter beyond limits. Inverter shuts down. Load transfers to bypass. | ||
| 
 | 
 | 
 | |
| System Transfer | The whole paralleled UPS system transferred to bypass at the same time. This message will | ||
| appear on the UPS which passive transfer to bypass | |||
| 
 | 
 | ||
| Parallel Board Fault | Malfunction of the paralleling control circuits of this UPS module. Can cause “System Transfer” | ||
| to bypass. | |||
| 
 | 
 | ||
| 
 | 
 | Rectifier, inverter and battery converter were shutdown because DC bus voltage is too high. | |
| DC Bus Over Voltage | Check whether there is a fault in rectifier side. If no, then check whether overload occurs. | ||
| 
 | 
 | Restart the inverter after resetting the fault | |
| 
 | 
 | The parallel cables are not connected correctly in a parallel system. | |
| Parallel Connect Fault | Reset the fault by pressing the “fault clear” button, then restart the inverter by pressing the | ||
| 
 | 
 | “inverter on” button. | |
| Bypass Over Current | Bypass current is over limit above 135% rating. The UPS just alarms and does nothing. | ||
| 
 | 
 | 
 | |
| LBS Active | 
 | Load Bus Synchronisation is active. The UPS is acting as an LBS master or slave in a dual bus | |
| 
 | configuration. | ||
| 
 | 
 | ||
| Setting Save Error | History records not saved. (Reserved) | ||
| 
 | 
 | ||
| Mains Neutral Lost | AC Input mains reference neutral not detected. | ||
| 
 | 
 | ||
| Protocol version clash | Firmware incompatibility between Monitor Board and Digital Signal Processor Board. | ||
| 
 | 
 | ||
| Battery ground fault | Battery leakage to ground detected (option) | ||
| 
 | 
 | ||
| Inv. Turned On Manually | Manual Turn On via front panel | ||
| 
 | 
 | ||
| Inv. Turned Off Manually | Manual Turn Off via front panel | ||
| 
 | 
 | 
 | |
| EPO | 
 | Emergency Power Off direct access key pressed or external command received | |
| 
 | 
 | 
 | |
| Transfer Confirm | Prompt to press “enter” key to acknowledge that an interrupted load transfer to bypass will | ||
| happen. | |||
| 
 | 
 | ||
| Transfer Cancel | Prompt to press “ESC” key to avoid that an interrupted load transfer to bypass will happen. | ||
| 
 | 
 | 
 | |
| Unit Off Confirm | Prompt to press “enter” key to acknowledge that the UPS will be disconnected from other | ||
| paralleled UPS modules. | |||
| 
 | 
 | ||
| System Off Confirm | Prompt to press “enter” key to acknowledge that the all paralleled UPS will be disconnected | ||
| from the load. | |||
| 
 | 
 | ||
62
