Operator Control Panel and Display

Table 22

UPS messages (continued)

 

 

 

Message

 

Description / Suggested Action (if any)

 

 

The UPS is confirmed to overload and the overload times out.

 

 

Note 1: the highest loaded phase will indicate overload timing-out first.

 

 

Note 2: When the timer is active then alarm “unit overload” should also be active as the load is

 

 

above nominal.

 

 

Note 3: When the timer has expired, the inverter Static Switch is opened and the load

Unit Over load Timeout

transferred to bypass. The inverter shutdown and will restart after 10 seconds.

 

 

Note 4: If the load decreases lower than 95% after 5 minutes, the system will transfer back to

 

 

inverter mode.

 

 

Confirm that the alarm is genuine by checking the load percent indicated on the LCD. If an

 

 

overload is indicated then check the load, and investigate any additional load connected prior to

 

 

the alarm (if applicable).

Byp. Abnormal Shutdown

Both bypass and inverter voltages unavailable. Load interruption

 

 

Inverter Over Current

Inverter Pulse Width Modulation module overloaded.

 

 

 

 

 

The phase sequence direction of bypass voltage is reversed.

 

 

Normally, the phase of phase B lags 120 degrees behind phase A, and the phase of phase C

Bypass Phase Reversed

lags 120 degrees behind phase B.

 

 

Verify that the phase rotation of the bypass supply presented to the UPS is correct, and rectify it

 

 

if it is found to be in error

Load Impact Transfer

A transfer to bypass occurred due to a large step load. The UPS should recover automatically.

Turn on connected equipment in sequential order to reduce the step loading of the inverter.

 

 

 

 

The load is on bypass power due to excessive number of transfers that occurred within the last

Transfer Time-out

hour.

The UPS will recover automatically and will transfer the load back to inverter power within an

 

 

 

 

hour.

 

 

Load Sharing Fault

UPS modules within a parallel system are not sharing the load current equally.

 

 

DC Bus Abnormal

DC input voltage to inverter beyond limits. Inverter shuts down. Load transfers to bypass.

 

 

 

System Transfer

The whole paralleled UPS system transferred to bypass at the same time. This message will

appear on the UPS which passive transfer to bypass

 

 

Parallel Board Fault

Malfunction of the paralleling control circuits of this UPS module. Can cause “System Transfer”

to bypass.

 

 

 

 

Rectifier, inverter and battery converter were shutdown because DC bus voltage is too high.

DC Bus Over Voltage

Check whether there is a fault in rectifier side. If no, then check whether overload occurs.

 

 

Restart the inverter after resetting the fault

 

 

The parallel cables are not connected correctly in a parallel system.

Parallel Connect Fault

Reset the fault by pressing the “fault clear” button, then restart the inverter by pressing the

 

 

“inverter on” button.

Bypass Over Current

Bypass current is over limit above 135% rating. The UPS just alarms and does nothing.

 

 

 

LBS Active

 

Load Bus Synchronisation is active. The UPS is acting as an LBS master or slave in a dual bus

 

configuration.

 

 

Setting Save Error

History records not saved. (Reserved)

 

 

Mains Neutral Lost

AC Input mains reference neutral not detected.

 

 

Protocol version clash

Firmware incompatibility between Monitor Board and Digital Signal Processor Board.

 

 

Battery ground fault

Battery leakage to ground detected (option)

 

 

Inv. Turned On Manually

Manual Turn On via front panel

 

 

Inv. Turned Off Manually

Manual Turn Off via front panel

 

 

 

EPO

 

Emergency Power Off direct access key pressed or external command received

 

 

 

Transfer Confirm

Prompt to press “enter” key to acknowledge that an interrupted load transfer to bypass will

happen.

 

 

Transfer Cancel

Prompt to press “ESC” key to avoid that an interrupted load transfer to bypass will happen.

 

 

 

Unit Off Confirm

Prompt to press “enter” key to acknowledge that the UPS will be disconnected from other

paralleled UPS modules.

 

 

System Off Confirm

Prompt to press “enter” key to acknowledge that the all paralleled UPS will be disconnected

from the load.

 

 

62

Page 70
Image 70
Liebert NX UPS System user manual UPS is confirmed to overload and the overload times out