Options—For Assembly Inside the UPS Cabinet

8.0OPTIONS—FOR ASSEMBLY INSIDE THE UPS CABINET

Several items of optional equipment are available for connection to the Liebert NX UPS. These are described in this section of the manual and should be fitted prior to installation.

8.1Protection

8.1.1Battery Ground Fault Detection

In addition to any residual current device mounted externally and upstream the UPS or when optional isolation transformers are fitted to the UPS, an optional residual battery current device can be fitted to detect leakage current from the battery into the PE (Protective Earth) Residual current range monitored: 30~3000mA.

Power supply voltage for the set: AC230V (L-N);

When a battery ground fault is detected, an alarm will appear on the UPS display panel. An additional Dry contact fault Alarm signal is available for remote monitoring:

Table 24 Dry contact fault alarm signal is available for remote monitoring

Terminal

Name

Definition

21

Common

Battery Ground Fault Detection – can be

programmed as Alarm or Pre-Alarm

 

 

22

NC

 

 

 

 

24

NO

 

 

 

 

The Battery ground fault detection set contains one CT (current transformer) and one DC sensitive residual current monitor. The connection of this set for UPS is illustrated as follows.

Figure 36 Battery ground fault detection set connections

Battery

Batt +

Batt-N

Batt -

Current Transformer

W1-A358 (installedBCB or externally only)

Contactor

X

X

Socket

Output

 

Phase

 

Output

 

Neutral

K1 K2 I2 I2

A111

A214

Battery Ground Fault Detection Resys B470 (AC230)

 

Monitor Board

 

-U2

4

+12V

2

IN DRY-X3

 

BtG

 

UPS

66

Page 74
Image 74
Liebert NX UPS System user manual Protection, Battery Ground Fault Detection, Terminal Name Definition