8.0OPTIONS—FOR ASSEMBLY INSIDE THE UPS CABINET
Several items of optional equipment are available for connection to the Liebert NX UPS. These are described in this section of the manual and should be fitted prior to installation.
8.1Protection
8.1.1Battery Ground Fault Detection
In addition to any residual current device mounted externally and upstream the UPS or when optional isolation transformers are fitted to the UPS, an optional residual battery current device can be fitted to detect leakage current from the battery into the PE (Protective Earth) Residual current range monitored: 30~3000mA.
Power supply voltage for the set: AC230V
When a battery ground fault is detected, an alarm will appear on the UPS display panel. An additional Dry contact fault Alarm signal is available for remote monitoring:
Table 24 Dry contact fault alarm signal is available for remote monitoring
Terminal | Name | Definition | |
21 | Common | Battery Ground Fault Detection – can be | |
programmed as Alarm or | |||
|
| ||
22 | NC |
| |
|
|
| |
24 | NO |
| |
|
|
|
The Battery ground fault detection set contains one CT (current transformer) and one DC sensitive residual current monitor. The connection of this set for UPS is illustrated as follows.
Figure 36 Battery ground fault detection set connections
Battery
Batt +
Batt -
Current Transformer
Contactor
X
X
Socket | Output |
| Phase |
| Output |
| Neutral |
K1 K2 I2 I2
A111
A214
Battery Ground Fault Detection Resys B470 (AC230)
| Monitor Board |
| |
4 | +12V |
2 | IN |
| |
BtG | |
| UPS |
66