UPS Multi-Module Installation

3.2Paralleled UPS Modules

The basic installation procedure of a parallel system comprising two or more UPS modules is the same as that of single module system. The following sections only introduce the installation proce- dures specific to the parallel system.

3.2.1Cabinet Installation

Place the UPS modules side by side and interconnect as shown in Figure 14. The distribution panel (external bypass cabinet) is optional but recommended for ease of maintenance and system testing.

Figure 14 Typical 1+N system block diagram with common input supply, with separate batteries and optional output / bypass distribution panel

SUPPLIED BY OTHERS

INPUT MAINS

INPUT MAINS

SUPPLY L1, L2, L3, N

SUPPLY L1, L2, L3, N

UPS1 CB1

RECTIFER

FUSES

STATIC

SWITCH

SW1-C

UPS2

FUSES

CB1

RECTIFER

SW1-C

STATIC

SWITCH

CHARGER

CHARGER

BATTERY 1

BATTERY 2

INVERTER

INVERTER

 

SW1-D

SW1-A

SW1-A

L1, L2, L3, N

L1, L2, L3, N

Q1EXT

Q2EXT

QUPS

QBYP

 

Distribution Cabinet

TO LOAD

27

Page 35
Image 35
Liebert NX UPS System user manual Paralleled UPS Modules, Cabinet Installation, Distribution Cabinet