
UPS 
3.0UPS 
3.1General
The installation of a 
In addition to the local EPO push button on the front panel of the UPS module (that stops operation of that module), the UPS supports also a remote emergency stop to permit simultaneous 
NOTES
1. The remote emergency power off switch must be 
2.The open voltage supplied is 12VDC, < 20mA
3.This external emergency stop may be supplied with a second set of contacts that can be used to trip incoming mains or bypass supply circuit breakers supplied by others and fitted with remote trip units.
4.Normally Closed EPO - X2: 1&2, these terminals are supplied 
Figure 13 Emergency power off connections
UPS2
X2:3
X2:4 Monitor Board
| X2:3 | Monitor Board | 
| X2:4 | 
UPS1
EPO
UPS2
| X2:1 | Monitor Board | 
| X2:2 | 
| X2:1 | Monitor Board | |
| X2:2 | ||
| 
 | 
UPS1
EPO
26
