Operator Control Panel and Display
7.1.1Mimic Power Flow
The LEDs mounted on the mimic flow chart represent the various power paths and current UPS oper- ational status.
| Table 12 | Rectifier  | |
| 
 | 
 | 
 | 
| Green | 
 | Rectifier in Normal Operation | 
| 
 | 
 | 
 | 
| Flashing | 
 | Input AC Normal, but rectifier not operating | 
| Green | 
 | 
 | 
| Red | 
 | Rectifier Failed | 
| 
 | 
 | 
 | 
| Off | 
 | Rectifier Not operating, Input AC Not Available or out of normal range | 
| 
 | 
 | 
 | 
| Table 13 | Battery  | |
| 
 | 
 | 
 | 
| Green | 
 | Battery Normal, but discharging and powering the load | 
| 
 | 
 | 
 | 
| Flashing | 
 | Battery End of Discharge  | 
| Green | 
 | 
 | 
| 
 | 
 | Battery abnormal (Failed, Absent or Polarity Reversed) or Battery | 
| Red | 
 | Converter abnormal | 
| 
 | 
 | (Failed, overcurrent, overtemperature) | 
| Off | 
 | Battery and Converter Normal, Battery charging. | 
| 
 | 
 | 
 | 
| Table 14 | Bypass  | |
| Green | 
 | Load on Bypass power | 
| 
 | 
 | 
 | 
| Red | 
 | Bypass not available, out of normal range or Static bypass switch fault. | 
| 
 | 
 | 
 | 
| Off | 
 | Bypass Normal, load not on bypass | 
| 
 | 
 | 
 | 
| Table 15 | Inverter  | |
| 
 | 
 | 
 | 
| Green | 
 | Inverter Normal and powering the load | 
| 
 | 
 | 
 | 
| Flashing | 
 | Inverter ON, starting up, synchronising, | 
| Green | 
 | or standing by (ECO mode) | 
| Red | 
 | Inverter failed | 
| 
 | 
 | 
 | 
| Off | 
 | Inverter not operating | 
| 
 | 
 | 
 | 
| Table 16 | Load  | |
| Green | 
 | UPS output ON and Normal | 
| 
 | 
 | 
 | 
| Red | 
 | UPS output ON and Overloaded | 
| 
 | 
 | 
 | 
| Off | 
 | UPS output OFF. | 
| 
 | 
 | |
| Table 17 Status (Alarm)  | ||
| 
 | 
 | 
 | 
| Green | 
 | Normal Operation | 
| 
 | 
 | 
 | 
| Yellow | 
 | UPS Warning e.g. AC Input Failure | 
| 
 | 
 | 
 | 
| Red | 
 | UPS fault e.g. Fuse or Hardware failure | 
| 
 | 
 | 
 | 
7.1.2Audible Alarm (Buzzer)
UPS activity is accompanied by the following sounds
Table 18 Audible alarm key
| Single beep | Direct Access key acknowledgement | 
| 
 | 
 | 
| One beep | UPS Warning e.g. AC Input Failure | 
| per second | 
 | 
| Continuous | Fault e.g. Fuse or Hardware failure | 
| beep | 
 | 