Single Module UPS Installation
1.8.4Output Dry Contacts
There are three output dry contact relays at the X1 slot (see Figure 5 and Table 6)
Figure 5 Output dry contacts and EPO wiring
+12V
X1
J13
| J21 | J25 | 
J28
X2
| BFP C | BFP S | BFP O | 
| INV C | INV S | INV O | ACF C | ACF S | ACF O | 
EPO - NO EPO - NC
| Table 6 | Output dry contact relays | ||
| Position | 
 | Name | Description | 
| J13.2 | 
 | BFP_O | Bypass feedback protection relay; normally open; closed when bypass SCR is shorted | 
| 
 | 
 | 
 | 
 | 
| J13.3 | 
 | BFP_S | Bypass feedback protection relay center | 
| 
 | 
 | 
 | 
 | 
| J13.4 | 
 | BFP_C | Bypass feedback protection relay; normally closed; open when bypass SCR is shorted | 
| 
 | 
 | 
 | 
 | 
| J21.2 | 
 | INV_O | Inverter mode relay; normally open; closed when UPS is in inverter mode | 
| 
 | 
 | 
 | 
 | 
| J21.3 | 
 | INV_S | Inverter mode relay center | 
| 
 | 
 | 
 | 
 | 
| J21.4 | 
 | INV_C | Inverter mode relay; normally closed. Opened when UPS is in inverter mode | 
| 
 | 
 | 
 | 
 | 
| J25.2 | 
 | ACF_O | Main input fault relay; normally open. Closed when main input is in fault | 
| 
 | 
 | 
 | 
 | 
| J25.3 | 
 | ACF_S | Main input fault relay center | 
| 
 | 
 | 
 | 
 | 
| J25.4 | 
 | ACF_C | Main input fault relay; normally closed. Open when main input is in fault | 
| 
 | 
 | 
 | 
 | 
NOTE
All auxiliary cables of terminal must be 
14