Single Module UPS Installation

1.8.4Output Dry Contacts

There are three output dry contact relays at the X1 slot (see Figure 5 and Table 6)

Figure 5 Output dry contacts and EPO wiring

+12V

X1

J13

J21

J25

J28

X2

BFP C

BFP S

BFP O

INV C

INV S

INV O

ACF C

ACF S

ACF O

EPO - NO EPO - NC

Table 6

Output dry contact relays

Position

 

Name

Description

J13.2

 

BFP_O

Bypass feedback protection relay; normally open; closed when bypass SCR is shorted

 

 

 

 

J13.3

 

BFP_S

Bypass feedback protection relay center

 

 

 

 

J13.4

 

BFP_C

Bypass feedback protection relay; normally closed; open when bypass SCR is shorted

 

 

 

 

J21.2

 

INV_O

Inverter mode relay; normally open; closed when UPS is in inverter mode

 

 

 

 

J21.3

 

INV_S

Inverter mode relay center

 

 

 

 

J21.4

 

INV_C

Inverter mode relay; normally closed. Opened when UPS is in inverter mode

 

 

 

 

J25.2

 

ACF_O

Main input fault relay; normally open. Closed when main input is in fault

 

 

 

 

J25.3

 

ACF_S

Main input fault relay center

 

 

 

 

J25.4

 

ACF_C

Main input fault relay; normally closed. Open when main input is in fault

 

 

 

 

NOTE

All auxiliary cables of terminal must be double-insulated. Wire should be 0.5-1.5mm2

(16-20AWG) stranded for maximum runs between 25 and 50 meters (82-164ft.) respectively.