Technical Specifications
Table 34 Battery
|
|
|
| Intermediate DC Circuit |
|
|
|
|
| |||||
Rated Power, |
| Unit of |
|
|
|
|
|
|
|
|
|
|
|
|
kVA |
| Measurement |
| 10 |
|
| 15 |
|
| 20 |
|
| 30 | |
Battery Bus |
| VDC |
|
| Nominal: 480V (VRLA Float charge is 540V) |
| ||||||||
Voltage |
|
|
|
|
| Range: 400V - 616V |
| |||||||
|
|
|
|
|
|
| ||||||||
Number of Lead- | Acid Cells |
|
|
|
|
|
|
|
|
|
|
|
| |
Nominal |
|
|
|
|
| 240 = [40 x |
| |||||||
Maximum |
|
|
|
|
| 264 = [44 x |
| |||||||
Float Voltage |
| V/cell (VRLA) |
|
| 2.25 V/cell (selectable from 2.2 |
| ||||||||
|
| Constant current and constant voltage (IU) charge mode | ||||||||||||
|
|
|
| |||||||||||
Temperature |
| mV/°C/cl |
| - 3.0 (selectable 0 to – 5.0 around 25°C or 30°C. or inhibit) | ||||||||||
Compensation |
|
| ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Ripple Voltage |
| % V float |
|
|
|
|
| ≤1 |
|
|
|
|
| |
Ripple Current |
| % C10 |
|
|
|
|
| ≤5 |
|
|
|
|
| |
Boost Voltage |
| V/cell (VRLA) |
|
| 2.35 V/cell (selectable from |
| ||||||||
|
| Constant current and constant voltage (IU) charge mode | ||||||||||||
|
|
|
| |||||||||||
|
|
|
| - | ||||||||||
Boost Control |
|
|
| - | (selectable | |||||||||
|
|
|
|
| 24 hr safety timeout (selectable |
| ||||||||
|
|
|
|
|
| - boost mode inhibit also selectable |
| |||||||
End Of |
|
|
|
| 1.63 V/cell (selectable from 1.60~1.75 V/cell |
| ||||||||
| V/cell (VRLA) |
| Auto Inverse EOD voltage x discharge current mode |
| ||||||||||
Discharge |
|
|
| |||||||||||
|
|
| (The end of discharge voltage increases at low discharge currents). | |||||||||||
|
|
|
| |||||||||||
|
|
|
|
| 2.4 V/cell (selectable from |
| ||||||||
Battery Charge |
| V/cell |
| Constant current and constant voltage (IU) charge mode | ||||||||||
|
|
|
| Programmable auto trigger or inhibit of boost mode |
| |||||||||
Battery |
| kW |
| 2.5 |
|
| 5 |
|
| 5 |
|
| 7.5 | |
Charging Power* |
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
max current |
| A |
| 3.75 |
|
| 7.5 |
|
| 7.5 |
|
| 12 | |
(adjustable) 1 |
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
* At low input voltage | the UPS recharge capability increases with load decrease (up to the maximum capacity indicated) | |||||||||||||
1. Max currents listed are for EOD voltage of 1.67 V/cell for 240 cells. |
|
|
|
|
|
|
|
| ||||||
Table 35 Inverter output to critical load |
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Unit of |
|
|
|
|
|
|
|
|
|
|
Rated Power, kVA (kW) | Measurement | 10 (8) |
| 15 (12) |
| 20 (16) |
|
| 30 (24) | |||||
Rated AC Voltage 1 |
| VAC |
| 380/400/ | 415 V | |||||||||
|
|
|
|
|
|
|
| referenced to the bypass neutral) |
| |||||
Frequency 2 |
|
| Hz |
|
|
|
|
| 50 / 60 |
|
|
| ||
|
|
|
|
|
|
|
|
| 110% for 60 min |
| ||||
Overload |
|
| % Rated |
|
|
|
| 125% for 10 min |
| |||||
|
|
|
|
|
| 150% for 1 min |
| |||||||
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
| >150% for 200 msec |
| |||||
Fault Current |
|
| % Rated |
|
| 340% current limitation for 200 msec |
| |||||||
Non linear load capability 3 |
| % Rated |
|
|
|
|
| 100% |
|
|
| |||
Neutral current capability |
| % Rated |
|
|
|
|
| 170% |
|
|
| |||
Steady state voltage stability | % |
| ±1 (balanced load), ±2 (100% unbalanced load), | |||||||||||
Transient voltage response 4 | % |
|
|
|
|
| ± 5 |
|
|
| ||||
Total Harmonic Voltage | % |
|
| < 1 (linear load), < 4 (non linear load 3) | ||||||||||
Distortion (THDV) |
|
|
|
|
|
|
|
|
|
|
|
|
| |
Synchronisation - Window |
|
|
| Rated frequency ± 2Hz (selectable ± 0.5 to ± 3Hz) | ||||||||||
Slew Rate (Max change rate |
|
|
|
|
|
|
| 1 Hz/sec |
| |||||
| Hz sec |
|
| selectable 0.1 to 3Hz/s (single UPS) |
| |||||||||
of synch frequency) |
|
|
|
| ||||||||||
|
|
|
|
| 0.2Hz/sec (paralleled UPS) |
| ||||||||
|
|
|
|
|
|
|
|
| ||||||
Inverter Voltage Tolerance |
| %V (AC) |
|
|
|
|
| ±5 |
|
|
|
1.Factory set to 400V – 380 or 415V selectable by commissioning engineer.
2.Factory set to 50Hz; 60 Hz selectable by commissioning engineer. Frequency converter operation also selectable.
3.EN
4.IEC
75