Technical Specifications

Table 34 Battery

 

 

 

 

Intermediate DC Circuit

 

 

 

 

 

Rated Power,

 

Unit of

 

 

 

 

 

 

 

 

 

 

 

 

kVA

 

Measurement

 

10

 

 

15

 

 

20

 

 

30

Battery Bus

 

VDC

 

 

Nominal: 480V (VRLA Float charge is 540V)

 

Voltage

 

 

 

 

 

Range: 400V - 616V

 

 

 

 

 

 

 

 

Number of Lead-

Acid Cells

 

 

 

 

 

 

 

 

 

 

 

 

Nominal

 

 

 

 

 

240 = [40 x 6-cell (12V) blocks]

 

Maximum

 

 

 

 

 

264 = [44 x 6-cell (12V) blocks]

 

Float Voltage

 

V/cell (VRLA)

 

 

2.25 V/cell (selectable from 2.2 –2.3V/cell)

 

 

 

Constant current and constant voltage (IU) charge mode

 

 

 

 

Temperature

 

mV/°C/cl

 

- 3.0 (selectable 0 to – 5.0 around 25°C or 30°C. or inhibit)

Compensation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ripple Voltage

 

% V float

 

 

 

 

 

≤1

 

 

 

 

 

Ripple Current

 

% C10

 

 

 

 

 

≤5

 

 

 

 

 

Boost Voltage

 

V/cell (VRLA)

 

 

2.35 V/cell (selectable from 2.30-2.40V/cell)

 

 

 

Constant current and constant voltage (IU) charge mode

 

 

 

 

 

 

 

 

- float-boost current trigger 0.050 C10 (selectable 0.030-0.070)

Boost Control

 

 

 

- boost-float current trigger 0.010 C10

(selectable 0.005-0.025) with

 

 

 

 

 

24 hr safety timeout (selectable 8-30 hr)

 

 

 

 

 

 

 

- boost mode inhibit also selectable

 

End Of

 

 

 

 

1.63 V/cell (selectable from 1.60~1.75 V/cell

 

 

V/cell (VRLA)

 

Auto Inverse EOD voltage x discharge current mode

 

Discharge

 

 

 

 

 

 

(The end of discharge voltage increases at low discharge currents).

 

 

 

 

 

 

 

 

 

2.4 V/cell (selectable from 2.3-2.4V/cell)

 

Battery Charge

 

V/cell

 

Constant current and constant voltage (IU) charge mode

 

 

 

 

Programmable auto trigger or inhibit of boost mode

 

Battery

 

kW

 

2.5

 

 

5

 

 

5

 

 

7.5

Charging Power*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

max current

 

A

 

3.75

 

 

7.5

 

 

7.5

 

 

12

(adjustable) 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* At low input voltage

the UPS recharge capability increases with load decrease (up to the maximum capacity indicated)

1. Max currents listed are for EOD voltage of 1.67 V/cell for 240 cells.

 

 

 

 

 

 

 

 

Table 35 Inverter output to critical load

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit of

 

 

 

 

 

 

 

 

 

 

Rated Power, kVA (kW)

Measurement

10 (8)

 

15 (12)

 

20 (16)

 

 

30 (24)

Rated AC Voltage 1

 

VAC

 

380/400/

415 V (three-phase, four-wire with neutral

 

 

 

 

 

 

 

 

referenced to the bypass neutral)

 

Frequency 2

 

 

Hz

 

 

 

 

 

50 / 60

 

 

 

 

 

 

 

 

 

 

 

 

110% for 60 min

 

Overload

 

 

% Rated

 

 

 

 

125% for 10 min

 

 

 

 

 

 

 

150% for 1 min

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

>150% for 200 msec

 

Fault Current

 

 

% Rated

 

 

340% current limitation for 200 msec

 

Non linear load capability 3

 

% Rated

 

 

 

 

 

100%

 

 

 

Neutral current capability

 

% Rated

 

 

 

 

 

170%

 

 

 

Steady state voltage stability

%

 

±1 (balanced load), ±2 (100% unbalanced load),

Transient voltage response 4

%

 

 

 

 

 

± 5

 

 

 

Total Harmonic Voltage

%

 

 

< 1 (linear load), < 4 (non linear load 3)

Distortion (THDV)

 

 

 

 

 

 

 

 

 

 

 

 

 

Synchronisation - Window

 

 

 

Rated frequency ± 2Hz (selectable ± 0.5 to ± 3Hz)

Slew Rate (Max change rate

 

 

 

 

 

 

 

1 Hz/sec

 

 

Hz sec

 

 

selectable 0.1 to 3Hz/s (single UPS)

 

of synch frequency)

 

 

 

 

 

 

 

 

 

0.2Hz/sec (paralleled UPS)

 

 

 

 

 

 

 

 

 

 

Inverter Voltage Tolerance

 

%V (AC)

 

 

 

 

 

±5

 

 

 

1.Factory set to 400V – 380 or 415V selectable by commissioning engineer.

2.Factory set to 50Hz; 60 Hz selectable by commissioning engineer. Frequency converter operation also selectable.

3.EN 50091-3 (1.4.58) crest factor 3:1

4.IEC 62040-3 / EN 50091-3 also for 0-100-0% load transient. Transient recovery time: return to within 5% of steady state output voltage within half a cycle.