Transmitting the Screen Data

Section 6-6

Ver 4.12

Select Transmit Mode.

Select Tool Transmit.

Precautions to Be Observed When Transmitting Screen Data

4.Open the screen data to be transmitted at the Support Tool, then select Download (NTST PT) in the Support Tool’s Connect menu and specify the data to be transmitted.

5.During screen data transmission, the transmission status is displayed.

6.On completion of screen data transmission, press the Quit touch switch. The NT631/NT631C returns to the Transmit mode.

If the screen data cannot be successfully transmitted from the Support Tool, use the communications check functions of the NT631/NT631C to check if communications between the NT631/NT631C is normal or not (page 209).

If any of the following, or a system error, occurs during transmission of screen data, the transmitted screen data will not be registered correctly in the NT631/ NT631C. If this happens, the NT631/NT631C may not enter the RUN mode when started up, or there may be unpredictable malfunctions such as failure to display screens during operation. In this case, the screen data must be retransmitted in file units to register it correctly.

The power to the NT631/NT631C is interrupted or the NT631/NT631C is reset.

The power to the personal computer on which the Support Tool is running is interrupted or the computer is reset.

The cable connecting the NT631/NT631C to the personal computer on which the Support Tool is running is disconnected or has a broken wire.

The Quit touch switch on the NT631/NT631C screen is pressed to end screen data transmission.

151