Connecting to the Host’s RS-422A/485 Port

 

Section 5-2

 

 

 

 

 

 

PLC

CPU Unit with built-in Host

CPU Units Connectable with

Host Link Unit or

 

Connectable

Series

Link

Host Link Units or

Communications Board/

 

to

 

 

Expansion Communications

Unit

 

 

 

 

Board/Units

 

 

 

 

 

 

 

 

 

CV Series

CV500-CPU01-EV1

CV500-CPU01-EV1

CV500-LK201

 

CV500

(*3)

CV1000-CPU01-EV1

CV1000-CPU01-EV1

 

 

CV1000

 

 

 

 

 

 

 

CV2000-CPU01-EV1

CV2000-CPU01-EV1

 

 

CV2000

 

 

 

 

 

 

CVM1

CVM1-CPU01-EV2

CVM1-CPU01-EV2

CV500-LK201

 

CVM1

Series (*3)

CVM1-CPU11-EV2

CVM1-CPU11-EV2

 

 

 

 

CVM1-CPU21-EV2

CVM1-CPU21-EV2

 

 

 

 

 

 

 

 

 

SRM1

SRM1-C02-V1+CPM1-CIF11

 

 

 

SRM1

 

 

 

 

 

 

*1 This CPU Unit is for a Duplex-CPU Unit System. The CS1W-SCB41(-V1) Serial Communications Board cannot be used.

*2 Use a CPM2C-CN111 or CS1W-CN114/118 Connecting Cable, CPM1- CIF01 RS-232C Adapter, or CPM1-CIF11 RS-422A Adapter to connect.

*3 CPU Units of CVM1/CV-series PLCs without the suffix -EV@cannot be connected.

The host link method cannot be used when an NT631/NT631C is connected using RS-485. To use the host link method, connect by RS-422A.

Settings at the Host

When using the RS-422A host link method, the settings shown below must be made at the host (depending on the Unit, some of these settings may not be necessary, or settings not shown here may be necessary).

Item

Setting at Host

 

 

I/O port

RS-422A

 

 

Communications speed

Set the same speed as for the NT631/NT631C. (*1)

Transfer code

ASCII, 7 data bits, 2 stop bits

 

 

Parity

Even

 

 

1-to-1/1-to-N

1-to-N(*2)

Instruction level

Level 1, 2, 3

 

 

Unit #

00

 

 

*1

*2

Set the host link communications speed at 9600 bps or 19200 bps with the Comm. Speed memory switch at the NT631/NT631C. For details, refer to 6- 7-2 Setting the Host Link Method (page 155).

The 1-to-N setting enables BCC (Block Check Character). It is not actually possible to connect more than one NT631/NT631C in a single host link.

The setting methods for each type of Unit are described in the following.