Connecting to the Host’s RS-422A/485 Port

Section 5-2

C1000H/C2000H Rack-mounting Unit: C500-LK203

Setting the Rear Switches

I/O port selection (selector switch) Set this to RS-422A.

5 V supply

 

 

ON

 

 

OFF

8

SW1

I/O port

7

 

6

 

RS-422A

5

 

RS-232C

4

 

 

3

 

Synchronization

2

 

1

 

Internal

ON

 

External

 

 

Terminator

8

 

7

 

OFF

 

6

SW2

ON

5

 

 

 

CTS

4

 

3

 

0 V

2

 

External

1

 

 

ON

 

Unit #, parity, and transfer code (DIP SW1-1 to SW1-7)

Set SW1-1 to SW1-7 to OFF (0).

Synchronization (selector switch) Set this to Internal.

Communications speed (DIP SW2-1 to SW2-4)

Set these switches to 0010 to select 19,200 bps.

Set these switches to 1010 to select 9,600 bps.

(0: OFF 1: ON)

1-to-1/1-to-N selection (DIP SW2-6) Set SW2-6 to OFF (0) (1-to-N).

Instruction level (DIP SW2-7, SW2-8) Set these switches to ON (1). (Levels 1, 2, and 3 are enabled.)

CTS selection (selector switch) Set this always to 0 V (ON).

Terminator setting (selector switch) Set this switch to ON.

C200H/C1000H/C2000H CPU-mounting Unit: 3G2A6-LK202-EV1

Setting the Rear Switches

SW1

SW2

SW3

Unit #, parity, and transfer code (DIP SW1-1 to SW1-5)

Set SW1-1 to SW1-5 to OFF (0).

*Parity is fixed at Even Parity. Transfer code is fixed at ASCII 7 data bits and 2 stop bits.

Communications speed (DIP SW2-1 to SW2-4) Set these switches to 0010 to select 19200 bps. Set these switches to 1010 to select 9600 bps.

(0: OFF 1: ON)

1-to-1/1-to-N selection (DIP SW2-6) Set SW2-6 to OFF (0) (1-to-N).

Instruction level (DIP SW2-7, SW2-8)

Set these switches to ON (1). (Levels 1, 2, and 3 are enabled.)

Terminator setting (DIP SW3-1 to SW3-6) Set SW3-1, SW3-3, and SW3-5 to ON (1). Set SW3-2, SW3-4, and SW3-6 to OFF (0). (Set terminator ON.)