Responding to Displayed Error MessagesSection 7-2

7-2-3

Errors Occurring on Screen Data Initialization and Transmission

 

 

The table below shows the errors that can occur when the NT631/NT631C

 

 

data is initialized, and during data setting and transmission, and their reme-

 

 

dies.

 

 

 

 

 

 

Message

Cause

Remedy

 

 

 

[Flash Memory Error]

There is a hardware fault, or the

If the same message is displayed even after

Flash Memory I/O Error.

flash memory (memory for storing

clearing the screen data or transmitting screen

screen data) has reached the end

data several times, contact your OMRON service

If this happens frequently, Flash

of its service life.

center.

Memory may be broken.

 

 

Press Reset Switch to restart.

 

 

 

 

 

[Calendar Data Error]

Hardware fault, or system pro-

Set the calendar clock again from the System

Calendar Data is incorrect.

gram error

Menu. If the problem recurs, delete the program

 

in the System Installer mode, then re-install the

Set to the MAINTENANCE MODE

 

 

program. (6-5-2 Clearing/Installing the System

and set Calendar Data.

 

 

Program, page 145)

 

 

 

 

 

 

If this does not solve the problem, contact your

 

 

 

OMRON service center.

 

 

 

[Tool Transmit Error]

The connecting cable is defective.

Check the cable connection and perform a con-

∗∗∗∗ Error detected while down-

 

ductivity test. If there is a fault, replace the cable.

loading by the following case:

 

(Appendix F Making the Cable for Connecting a

 

PLC)

• faulty connecting cable.

 

 

 

Malfunction due to external noise

Carry out grounding work in accordance with the

• corrupted data by noise.

 

conditions by referring to 3-1-4 Grounding,

 

 

 

 

 

 

page 34.

 

 

 

[Tool Transmit Error]

Malfunction due to external noise

Carry out grounding work in accordance with the

Check Sum Error occurs while

 

conditions by referring to 3-1-4 Grounding,

 

page 34.

downloading by the following

 

 

 

case:

 

 

 

• corrupted data by noise.

 

 

 

 

 

[Tool Transmit Error]

The connecting cable is defective.

Check the cable connection and perform a con-

Time-out Error occurs while down-

 

ductivity test. If there is a fault, replace the cable.

 

 

loading by the following case:

 

 

• faulty connecting cable.

 

 

 

 

 

[Tool Transmit Error]

The receive buffer has overflowed.

Retransmit the data from the Support Tool.

Reception was failed by Buffer

 

 

Over Flow Error.

 

 

 

 

 

 

7-2-4

Errors in the System Installer Mode and Their Remedies

 

 

This section describes the errors that may occur in the System Installer mode

 

 

of the NT631/NT631C, and the remedies for these errors.

 

 

 

 

 

 

Message

 

Cause

Remedy

 

 

 

 

System Program not exist or

-

The system program has not

Select Download System Program and download

incorrect.

 

 

been installed.

the system program (6-5-2 Clearing/Installing the

 

 

-

The system program has been

System Program, page 145)

 

 

 

 

 

 

deleted due to a hardware fault,

If this does not solve the problem, contact your

 

 

 

or because the flash memory

OMRON service center.

 

 

 

(memory for storing the system

 

 

 

 

program) has reached its life.

 

 

 

 

Unable to erase System Program.

Hardware fault, or flash memory

If the same message is displayed on repeating

 

 

(memory for storing the system

selection of Download System Program and

 

 

program) has reached its life.

attempting to delete the system program several

 

 

 

 

times, contact your OMRON service center (6-5-2

 

 

 

 

Clearing/Installing the System Program,

 

 

 

 

page 145)

232

Page 249
Image 249