Connecting to the RS-232C Port at the Host

Section 4-1

Note Cannot be used with the CS1D-CPU65H/67H.

CPU Unit Allocation DM Area Settings

Setting is written from the Programming Device (a Programming Console or CX-Programmer) directly into the allocation DM area (system setting area) of the CPU Unit. After the setting is written, it becomes effective by turning the power ON, restarting the Unit, restarting the communications port, or execu- tion of the STUP command.

In the following, the channel numbers of the allocation DM area and settings are shown.

Allocated DM Area words

Setting

Setting Contents

 

 

 

 

Port 1

Port 2

 

 

 

 

 

 

DM32000

DM32010

8200

1:N NT Link Mode

 

 

 

 

DM32001

DM32011

0000 to 0009 (*1)

Baud rate (standard)

DM32006

DM32016

000@

@ = The highest unit number of the

 

 

 

connected PTs (0 to 7)

*1 Set any value between 0000 and 0009 hex for the baud rate. The same baud rate will be used regardless of the value as long as it is between 0000 and 0009 hex.

When connecting PTs with model numbers 3 to 6 to port 1, for example, set the value 8200 hex to DM32000, 0000 hex to DM32001, and 0006 hex to DM32006.

Connecting to CS/CJ-series Serial Communications Unit

A CS/CJ-series Rack-mounting Unit:

CS1W-SCU21,

 

CJ1W-SCU21(-V1)/41(-V1)

Setting the Front Switches

Set the unit number of the Serial Communications Unit by using the rotary switch located on the front panel. Set each switch with a flat blade screwdriver so that the values or symbols in the setting value window agree with the fol- lowing.

SCU21

RUN

RDY

ERC

ERH

SD1

SD2

RD1

RD2

UNIT

F

No.

10

32

 

 

4

 

 

56789

Set the unit number to 0 through F so that it will not overlap with the numbers used in other units.

Allocation DM Area Settings for CPU Unit

Setting is written from the Programming Device (a Programming Console or CX-Programmer) directly into the allocation DM area (system setting area) of the CPU Unit. After the setting is written, it becomes effective by turning the power ON, restarting the Unit, restarting the communications port, or execu- tion of the STUP command.

In the following, the channel numbers of the allocation DM area and settings are shown.

m=DM30000+100*unit number (CH)

Allocated DM Area words

Setting

Setting Contents

 

 

 

 

Port 1

Port 2

 

 

 

 

 

 

m

m+10

8200

1:N NT Link Mode

 

 

 

 

m+1

m+11

0000 to 0009 (*1)

Baud rate (standard)

m+6

m+16

000@

@ = The highest unit number of the

 

 

 

connected PTs (0 to 7)