Connecting to the RS-232C Port at the Host

Section 4-1

PLC Setup Area Settings

When connecting to a C200HS, C200HX/HG/HE(-Z)E, CPM1, CPM2A, CPM2C, CQM1, or CQM1H CPU Unit, or SRM1, set the following communi- cations conditions for the PLC Setup area.

Item

Setting at Host

 

 

Communications mode

Host link mode

 

 

Communications speed

Set the same speed as set at the NT631/NT631C(*1)

Stop bit

2 stop bits

 

 

Parity

Even

 

 

Data length

ASCII 7 bits

 

 

Unit #

00

 

 

*1 Set the host link communications speed at 9600 bps or 19200 bps with the memory switch at the NT631/NT631C. For details, refer to 6-7-2 Setting the Host Link Method (page 155).

Set the PLC Setup area settings directly from a Programming Device (e.g.

CX-Programmer).

For details on operations relating to the PLC Setup area, refer to the manual for the PLC which is used.

The PLC Setup area word numbers and settings to be made depending on the Unit and port to which the connection is made are shown below.

CPM2A, CPM2C, CQM1H, or SRM1: Peripheral port connection

Word #

Writing Value

Settings

 

 

 

DM6650

0001

Host link mode, no CTS control

 

 

Communications conditions set by the contents of DM

 

 

 

DM6651

0303

Data length 7 bits, 2 stop bits, even parity, communica-

 

 

tions speed: 9600 bps

 

 

 

 

0304

Data length 7 bits, 2 stop bits, even parity, communica-

 

 

tions speed: 19200 bps

 

 

 

DM6653

0000

Unit # 00

 

 

 

C200HS, C200HX/HG/HE(-Z)E, CPM2A, CPM2C, CQM1, CQM1H (other than the CPU11), or SRM1: Built-in RS-232C port connection

Word #

Writing Value

Settings

 

 

 

DM6645

0001

Host link mode, no CTS control

 

 

Communications conditions set by the contents of DM

 

 

 

DM6646

0303

Data length 7 bits, 2 stop bits, even parity, communica-

 

 

tions speed: 9600 bps

 

 

 

 

0304

Data length 7 bits, 2 stop bits, even parity, communica-

 

 

tions speed: 19200 bps

 

 

 

DM6648

0000

Unit # 00

 

 

 

C200HX/HG/HE(-Z)E: Serial Communications Board port A

CQM1H: Serial Communications Board port 1

Word #

Writing Value

Settings

 

 

 

DM6555

0001

Host link mode, no CTS control

 

 

Communications conditions set by the contents of DM

 

 

 

56