Responding to Displayed Error Messages

Section 7-2

Probable Causes and Remedies

Overrun error

FCS (sum value) error

Time out error

Data over flow error

PLC unit No. error (Host Link only)

NAK received (in the case of the Host Link, the end code is also dis- played)

Undefined command error

Send Errors

The following errors can occur when receiving data.

Time out error

Data over flow error

The remedies to take in accordance with the displayed cause are indicated in the table below.

Error Details

Displayed Probable Cause

Remedy

 

 

 

Parity Error

Communications parameters/

Check if the settings at the host for parity bit, frame

Framing Error

conditions set incorrectly.

length, communications speed, stop bit length and

 

flow control agree with those at the NT631/NT631C.

Over-run Error

 

 

 

The connecting cables are not con-

Check the communications cable connection and

 

 

nected correctly.

perform a conductivity test. If there is a fault, replace

 

 

the cable. For details on communications cables,

 

 

refer to SECTION 4 Connecting to the Host from the

 

 

RS-232C Port, and SECTION 5 Connecting to the

 

 

Host from the RS-422A/485 Port.

 

 

 

 

Noise caused data corruption during

Carry out grounding work in accordance with the

 

communications.

conditions by referring to 3-1-4 Grounding, page 34.

 

 

 

FCS (Check Sum) Error

Noise caused data corruption during

Carry out grounding work in accordance with the

 

communications.

conditions by referring to 3-1-4 Grounding, page 34.

 

 

 

 

The PLC is transmitting incorrect

Check the operation at the host side.

 

data.

 

 

 

 

Time-out Error

The connecting cables are not con-

Check the communications cable connection and

 

nected correctly. (Send/Receive)

perform a conductivity test. If there is a fault, replace

 

 

the cable. For details on communications cables,

 

 

refer to SECTION 4 Connecting to the Host from the

 

 

RS-232C Port, and SECTION 5 Connecting to the

 

 

Host from the RS-422A/485 Port.

 

 

 

 

The communications service of the

Check that the host is capable of communicating with

 

host is stopped. (Send/Receive)

the NT631/NT631C (confirm that the communica-

 

 

tions settings of the host and NT631/NT631C match).

 

 

 

 

Time-out Interval is too short. (Send)

Set a longer value for Time-out Interval at the host

 

 

side.

 

 

 

 

Time-out Interval is too short.

Set a longer value for Time-out Interval in the System

 

(Receive)

Menu. (6-9-12 Setting the Time-out Interval,

 

 

page 181) It may also be possible to solve the prob-

 

 

lem by shortening the host cycle time.

 

 

 

PLC Unit No. Error

The unit # does not match that set on

Re-set the unit number at the host side to 0.

 

the PLC.

 

 

 

 

 

Noise caused data corruption during

Carry out grounding work in accordance with the

 

communications.

conditions by referring to 3-1-4 Grounding, page 34.

 

 

 