Omron NT631C manual Port selection selector switch Set this to RS-422A

Models: NT631 NT631C

1 315
Download 315 pages 48.17 Kb
Page 115
Image 115

Connecting to the Host’s RS-422A/485 Port

Section 5-2

Setting the Rear Switches

I/O port selection (selector switch) Set this to RS-422A.

I/O port

8

 

RS-422A

7

 

RS-232C

6

SW1

 

5

 

Synchronization

4

 

3

 

Internal

2

 

1

 

External

 

ON

 

 

 

Terminator

8

 

OFF

7

 

6

 

ON

SW2

5

 

 

CTS

4

 

3

 

0 V

2

 

External

1

 

 

ON

 

Unit # (DIP SW1)

Set SW1-1 to SW1-5 to OFF (0).

Synchronization (selector switch) Set this to Internal.

Communications speed

(DIP SW2-1 to SW2-4)

Set these switches to 0010 to select 19200 bps.

Set these switches to 1010 to select 9600 bps.

(0: OFF 1: ON)

1-to-1/1-to-N selection (DIP SW2-6) Set SW2-6 to OFF (0) (1-to-N).

Instruction level (DIP SW2-7, SW2-8) Set these switches to ON (1). (Levels 1, 2, and 3 are enabled.)

CTS selection (selector switch) Set this always to 0 V (ON).

Terminator setting (selector switch) Set this switch to ON.

98

Page 115
Image 115
Omron NT631C manual Port selection selector switch Set this to RS-422A