Connecting to the Host’s RS-422A/485 Port

Section 5-2

*3 CPU Units of CVM1/CV-series PLCs without the suffix -EV@cannot be connected.

The NT Link (1:1) method cannot be used using RS-485. To use the NT Link (1:1) method, connect by RS-422A.

The 1:1 NT Link connection using RS-422A/485 is not possible with the

CPM1, CPM2A, or CPM2C.

Settings at the Host

The setting methods for each type of Unit are described in the following.

Connecting to a CVM1/CV-series (-EV@) CPU Units

CV500-CPU01-EV1/CV1000-CPU01-EV1/CV2000-CPU01-EV1

CVM1-CPU01-EV2/CVM1-CPU11-EV2/CVM1-CPU21-EV2

PLC Setup

When connecting to a CVM1/CV-series CPU Unit by the NT Link (1:1) method, no particular settings are required at the PLC Setup.

Setting the Front Switches

I/O port selector switch

RS-232C

RS-422A

Host link communications method selection (selector switch)

Set this to RS-422A.

Communications type setting (DIP SW3)

Set this switch to ON.

(for communications by NT Link)

Terminator setting (DIP SW6)

Set this switch to ON. (Set terminator ON.)

• Connecting to a C-series C200HX/HG/HE(-Z)E

PLC Setup Area Settings

Write the PLC Setup area (data memory) settings directly from a Program- ming Device (e.g. CX-Programmer) in accordance with the host model.

Host Model

Word #

Setting

Setting Contents

 

 

 

 

Port A of C200HX/HG/HE(-Z)E*1

DM6555

4000

Use NT Link (1:1)

Port 2 of CQM1H*2

DM6550

4000

 

*1 RS-422A port of the Communications Board

*2 RS-422A port of the Serial Communications Board

For details on operations relating to the PLC Setup area, refer to the manual for the PLC you are using.