Connecting to the Host’s RS-422A/485 Port

Section 5-2

Using the NT Link (1:1) Method

 

 

 

 

m = DM 30000 + 100 unit number

 

 

 

Allocated DM Area

Setting

Setting Contents

 

words

 

 

 

 

 

 

 

Port 1

 

Port 2

 

 

 

 

 

 

 

m

 

m+10

8000

Host link mode, 2 stop bits,

 

 

 

 

even parity, data length 7 bits

 

 

 

 

 

m+1

 

m+11

0000

Communications speed: 9600 bps

 

 

 

 

 

 

 

 

0007

Communications speed: 19200 bps

 

 

 

 

 

m+2

 

m+12

0000

Transmit delay time 0 ms

 

 

 

 

 

m+3

 

m+13

0000

No CTS control Unit, No.0 for host link

 

 

 

 

 

Compatible Host Units

Some models and series of OMRON PLCs have the RS-422A NT Link (1:1) function built in.

The C200HX/HG/HE(-Z)E CPU Units can be connected by the RS-422A NT Link (1:1) method by installing a Communications Board.

The CQM1H CPU Units can be connected by the RS-422A NT Link (1:1) method by installing a Serial Communications Board.

Check the model and series of the PLC against the type of CPU Unit before making the connections.

The hosts that can be connected to the RS-422A port of the NT631/NT631C by the RS-422A NT Link (1:1) method are indicated in the table below.

PLC Series

CPU Units with Built-in RS-422A NT

Model Name

 

Link (1:1) Function

 

 

 

 

C Series

C200HE-CPU32-(Z)E(*1)

C200HE(-Z)E

 

C200HE-CPU42-(Z)E(*1)

 

 

C200HG-CPU33-(Z)E(*1)

C200HG(-Z)E

 

C200HG-CPU43-(Z)E(*1)

 

 

C200HG-CPU53-(Z)E(*1)

 

 

C200HG-CPU63-(Z)E(*1)

 

 

C200HX-CPU34-(Z)E(*1)

C200HX(-Z)E

 

C200HX-CPU44-(Z)E(*1)

 

 

C200HX-CPU54-(Z)E(*1)

 

 

C200HX-CPU64-(Z)E(*1)

 

 

C200HX-CPU65-ZE(*1)

 

 

C200HX-CPU85-ZE(*1)

 

 

CQM1H-CPU51/61

CQM1H

 

 

 

CV Series (*3)

CV500-CPU01-EV1

CV500

 

CV1000-CPU01-EV1

CV1000

 

 

 

 

CV2000-CPU01-EV1

CV2000

 

 

 

CVM1 Series (*3)

CVM1-CPU01-EV2

CVM1

 

CVM1-CPU11-EV2

 

 

CVM1-CPU21-EV2

 

 

 

 

*1 One of the following Communications Boards is required: C200HW-COM03-EV1 or C200HW-COM06-EV1.

*2 A CQM1H-SCB41-E Serial Communications Board is required.