Connecting to the Host’s RS-422A/485 Port

Section 5-2

PLC Setup Area Settings

When connecting to a C200HX/HG/HE(-Z)E or CPM1, CPM2A, CPM2C, CQM1H CPU Units or SRM1, set the following communications conditions for the PLC Setup area.

Item

Setting at Host

 

 

I/O port

RS-422A

 

 

Communications mode

Host link mode

 

 

Communications speed

Set the same speed as for the NT631/NT631C. (*1)

Stop bit

2 stop bits

 

 

Parity

Even

 

 

Data length

ASCII 7 bits

 

 

Unit #

00

 

 

*1 Set the host link communications speed at 9600 bps or 19200 bps with the Comm. Speed at the NT631/NT631C. For details, refer to 6-7-2 Setting the Host Link Method (page 155).

Set the PLC Setup area settings directly from a Programming Device (e.g.

CX-Programmer).

For details on operations relating to the PLC Setup area, refer to the manual for the PLC which is used.

The PLC Setup area word numbers and settings to be made depending on the Unit to which the connection is made are shown below.

When using port A of the Communications Board of C200HX/HG/HE(-Z)E

Word #

Setting

Setting Contents

 

 

 

DM6555

0001

Host link mode, no CTS control

 

 

Communications conditions set by the contents of DM

 

 

 

DM6556

0303

Data length 7 bits, 2 stop bits, even parity, communica-

 

 

tions speed: 9600 bps

 

 

 

 

0304

Data length 7 bits, 2 stop bits, even parity, communica-

 

 

tions speed: 19200 bps

 

 

 

DM6558

0000

Unit # 00

When using a CPM1, CPM2A, CPM2C, SRM1

Word #

Setting

Setting Contents

 

 

 

DM6650

0001

Host link mode, no CTS control

 

 

Communications conditions set by the contents of DM

 

 

 

DM6651

0303

Data length 7 bits, 2 stop bits, even parity, communica-

 

 

tions speed: 9600 bps

 

 

 

 

0304

Data length 7 bits, 2 stop bits, even parity, communica-

 

 

tions speed: 19200 bps

 

 

 

DM6653

0000

Unit # 00

 

 

 

When using a CQM1H

Word #

Setting

Setting Contents

 

 

 

DM6550

0001

Host link mode, no CTS control

 

 

Communications conditions set by the contents of DM

 

 

 

DM6551

0303

Data length 7 bits, 2 stop bits, even parity, communica-

 

 

tions speed: 9600 bps

 

 

 

 

0304

Data length 7 bits, 2 stop bits, even parity, communica-

 

 

tions speed: 19200 bps

 

 

 

DM6553

0000

Unit # 00

 

 

 

103

Page 120
Image 120
Omron NT631C manual When using a CPM1, CPM2A, CPM2C, SRM1, When using a CQM1H