Connecting to the Host’s RS-422A/485 Port

Section 5-2

Using the High-speed NT Link (1:N) Method

2-wire or 4-wire selector (WIRE): 4

(4-wire = RS-422A), or

2

(2-wire = RS-485)

Terminating resistance switch (TERM): ON (terminator ON = terminating resistance enabled).

DM Area Allocation Settings

From the Programming Device (i.e., a Programming Console or CX-Program- mer), write the settings directly to the CPU Unit's DM Area Setup Area. After the settings have been written, they will be enabled when the power supply is cycled, the Unit is restarted, the communications port is restarted, or a STUP instruction is executed.

The DM Area words that are allocated and the contents of the settings are given in the following table.

m = DM 30000 + 100 unit number

Allocated DM Area words

Setting

Setting Contents

 

 

 

 

Port 1

Port 2

 

 

 

 

 

 

m

m+10

8200

1:N NT Link Mode

 

 

 

 

m+1

m+11

0000 to 0009 (*1)

Baud rate (standard)

m+6

m+16

000@

@ = The highest unit number

 

 

 

of the connected PTs (0 to

 

 

 

7)

 

 

 

 

*1 Set any value between 0000 and 0009 hex for the baud rate. The same baud rate will be used regardless of the value as long as it is between 0000 and 0009 hex.

Compatible Host Units

Only OMRON’s CS/CJ-series PLCs support the high-speed 1:N NT Link through RS-422A/RS-485. The high-speed 1:N NT Link must be established through a Serial Communications Board/Unit. (Even CS/CJ-series Units with- out the “-V1” suffix can be connected via a high-speed 1:N NT Link by mount- ing a Serial Communications Board/Unit.)

Be sure to check the model number of the PLC and Board/Unit before trying to establish the high-speed 1:N NT Link.

The following table shows which CS-series PLCs can be connected to an NT631/NT631C with the high-speed 1:N NT Link through RS-422A/RS-485.

PLC

CPU Units with

CPU Unit that becomes

Model

Series

Built-in NT Link

connectable by installing a

Name

 

(1:1) Function

Communications Board/Unit

 

 

 

 

 

CS

 

CS1G-CPU42/43/44/45-E(V1)(*1)

CS1G

Series

 

CS1H-CPU63/64/65/66/67-E(V1)(*1)

CS1H

 

 

 

 

CS1G-CPU42H/43H/44H/45H(*1)

CS1D

 

 

 

 

 

CS1H-CPU63H/64H/65H/66H/67H(*1)

 

 

 

CS1D-CPU65H/67H(*2)

 

CJ

 

CJ1G-CPU44/45(*3)

CJ1G

Series

 

CJ1G-CPU42H/43H/44H/45H(*3)

CJ1H

 

 

 

 

CJ1H-CPU65H/66H/67H(*3)

CJ1M

 

 

 

 

 

CJ1M-CPU11/12/13/21/22/23(*3)

 

*1 A CS1W-SCB41(-V1) Serial Communications Board or CS1W-SCU31-V1 Serial Communications Unit is required.