Responding to Displayed Error Messages

Section 7-2

 

 

 

Message

Cause

Remedy

 

 

 

[No Starting Screen]

No data is registered for either the

Either specify a screen number for which

Specified Starting Screen is not saved.

screen number set in the PT sta-

data is registered at the PT status control

tus control area or the Initial

area, or set the screen as the Initial

Fix Screen Data using by the Support

Screen set with the Support Tool.

Screen in the System settings under PT

Tool.

Or the screen number which does

Configuration at the Support Tool.

Then set the PT to the TRANSMIT

not exist are registered.

 

MODE and download Screen Data again.

 

 

[Touch Panel is disconnected]

The touch panel cable (film cable)

If this message appears after the backlight

 

inside the NT631/NT631C is dis-

is replaced, reinstall the touch panel prop-

 

connected.

erly referring to Replacing the Backlight

 

 

(page 236). If the message keeps appear-

 

 

ing, contact your OMRON service center.

 

 

 

[Memory Switch Corrupted]

The memory switches have been

Set the memory switches again using the

Because Memory Switch setting was

initialized due to discovery of an

System Menu and the System settings

error in the memory switch set-

under PT Configuration at the Support

last. Initialized Memory Switch setting.

tings.

Tool. (SECTION 6 System Menu Opera-

Press Confirm to return to the SYSTEM

 

tion)

MENU.

 

 

If the problem recurs, contact your

 

 

 

 

OMRON service center.

 

 

 

[Calendar Data Error]

There is an error in the date/time

Check the battery voltage by checking the

Calendar Data is incorrect.

values due, for example, to low

color of the RUN LED and with the battery

battery voltage.

check in the System Menu; if the voltage is

Set to the MAINTENANCE MODE and

 

low, replace the battery with a new one.

set Calendar Data.

 

 

(Checking the Battery Voltage, page 208,

 

 

 

 

and 7-3-1 Replacing the Battery,

 

 

page 241)

 

 

If the battery voltage is confirmed to be

 

 

normal, set the calendar clock correctly

 

 

from the System Menu. (6-11-2 Display-

 

 

ing/Setting the Calendar and Clock,

 

 

page 191)

 

 

 

[Backup Data Error]

Initialization has been executed

Check the battery voltage by checking the

Memory table and History data was ini-

because of an error in the backup

color of the RUN LED and with the battery

data area.

check in the System Menu; if the voltage is

tialized by backup failure.

 

low, replace the battery with a new one.

It can be caused by lowered voltage of

 

 

(Checking the Battery Voltage, page 208,

the battery.

 

 

and 7-3-1 Replacing the Battery,

 

 

 

 

page 241)

 

 

The re-transmit the memory table data

 

 

from the Support Tool.

 

 

If the voltage is normal and the problem

 

 

recurs, contact your OMRON service cen-

 

 

ter.

 

 

 

[With memory switch setting screen]

Protocol settings for serial port A

Refer to Possible Combinations of Com-

Invalid Comm. Method

and serial port B are mismatched.

munications Method Settings on page 154

 

and set the protocol of serial port A and

 

 

 

 

serial port B so that their settings are

 

 

matched.

 

 

* Set serial port A to None when connect-

 

 

ing the Support Tool and the host at the

 

 

same time.

 

 

 

230

Page 247
Image 247
Omron NT631C manual Erly referring to Replacing the Backlight, Menu