SpecificationsAppendix A

For a Host Link, RS-422A

Item

 

Specification

 

 

 

Communications standard

EIA RS-422A

 

 

 

 

Communications settings

Start-stop synchronization

 

 

Communications speed: 9600, 19200 bps

 

Data length:

7 bits

 

Stop bit:

2 bits

 

Parity:

Even

 

 

Connector

Terminal Block (serial port B)

 

 

 

Number of Units connected

1:1

 

 

 

 

Transmission distance

Max. 500 m

 

 

 

 

Communications protocol

C-series SYSWAY (1:N)

 

 

 

 

For an NT Link, 1:1, RS-232C

Item

Specification

 

 

Communications standard

EIA RS-232C

 

 

Connector

9-pin D-SUB connector (female) (serial port A, B)

 

 

Number of Units connected

1:1

 

 

Transmission distance

Max. 15 m*

* When using an NT-AL001, the specifications are as follows.

RS-232C cable:

Max. 2 m

RS-422A cable:

Total length 500 m max.

For an NT Link, 1:1, RS-422A

Item

Specification

 

 

Communications standard

EIA RS-422A

 

 

Connector

Terminal block (serial port B)

 

 

Number of Units connected

1:1

 

 

Transmission distance

Max. 500 m

 

 

For an NT Link, 1:N, RS-232C

Item

Specification

 

 

Communications standard

EIA RS-232C

 

 

Connector

9-pin D-SUB connector (female) (serial port A, B)

 

 

Number of Units connected

1:1 to 8

 

 

Transmission distance

Max. 15 m*

*To connect two or more PTs, NT-AL001 Adapters are required. When using an NT-AL001, the specifications are as follows.

RS-232C cable:

RS-422A/485 cable:

Max. 2 m

Total length 500 m max.

251

Page 268
Image 268
Omron NT631C manual For a Host Link, RS-422A, For an NT Link, 11, RS-232C, For an NT Link, 11, RS-422A