Connecting to the RS-232C Port at the Host

 

Section 4-1

 

 

 

 

 

 

PLC Series

CPU Units with Built-in

CPU Units Connect-

Connectable to

 

 

NT Link Function

able with Expansion

 

 

 

 

Communications

 

 

 

 

Board(*1)

 

 

CVM1

CVM1-CPU01-EV2

 

CVM1

 

Series (*5)

CVM1-CPU11-EV2

 

 

 

 

CVM1-CPU21-EV2

 

 

 

 

 

 

 

 

CompoBus/

SRM1-C02-V1

 

SRM1

 

S Master

 

 

 

 

Control Unit

 

 

 

 

 

 

 

 

*1 One of the following Communications Boards is required: C200HW- COM02/COM04/COM05/COM06-EV1.

*2 A CPM1-CIF01 Adapter is required.

*3 Use a CPM2C-CN111 or CS1W-CN114/118 Connecting Cable, CPM1- CIF01 RS-232C Adapter, or CPM1-CIF11 RS-422A Adapter to connect.

*4 A CQM1H-SCB41 Serial Communications Board is required.

*5 CPU Units of CVM1/CV-series PLCs without the suffix -EV@cannot be connected.

Reference: CS/CJ-series CPU Units cannot be connected with the 1:1 connection NT link method. Use the 1:N connection NT link method (standard or high-speed) instead to make the 1:1 connection. For details, refer to Using the NT Link (1:N) Method (page 65) or Using the High-speed NT Link (1:N) Method (page 70).

Settings at the Host

The setting methods for each Unit are as follows.

Connecting to a C-series C200HS, C200HX/HG/HE(-Z)E, CPM1, CPM2A,

CPM2C, CQM1, CQM1H or SRM1 PLC

PLC Setup Area Settings

Write the PLC Setup area (data memory) settings directly from a Program- ming Device (e.g. CX-Programmer) in accordance with the host model and port.

Host Model

Word #

Writing Value

Setting

 

 

 

 

RS-232C port of C200HS, C200HX/

DM6645

4000

Use NT link

HG/HE(-Z)E, CPM2A, CPM2C,

 

 

(1:1)

CQM1, CQM1H, SRM1

 

 

 

 

 

 

 

Port A of C200HX/HG/HE(-Z)E (*1)

DM6555

 

 

Port 1 of CQM1H (*2)

 

 

 

Port B of C200HX/HG/HE(-Z)E (*1)

DM6550

 

 

CPM1

DM6650

 

 

 

 

 

 

*1 RS-232C port of the Communications Board

*2 RS-232C port of the Serial Communications Board

For details on operations relating to the PLC Setup area, refer to the manual for the PLC which is used.

63

Page 80
Image 80
Omron NT631C manual Setting methods for each Unit are as follows, Host Model Word # Writing Value Setting