Connecting to the RS-232C Port at the Host

Section 4-1

4-1 Connecting to the RS-232C Port at the Host

The method for connecting between the RS-232C port of the PT and the RS- 232C port of the host is as follows.

The following discussion is focused on the connection method to OMRON PLCs (By using the memory link method, a connection can be made to any arbitrary RS-232 unit). When making a connection to a host other than OMRON PLCs, refer to the PLC Connection Manual (V042-E1-@) or NT31/ 631 Multi Vendor Connection Manual (V060-E1-@).

Direct Connection Between The RS-232C Ports Using an RS-232C Cable (page 73)

This is the easiest connection method. Depending on the host to which the connection is to be made, it may be possible to use OMRON cables with con- nectors.

NT631/NT631C

Host

RS-232C cable (max. 15 m)

Reference: The CS/CJ-series CPU Unit cannot be connected with the 1:1 connection NT Link method. Use the 1:N connection NT Link method instead to make the 1:1 connection. For details, refer to Using the NT Link (1:N) Method (page 65) or Using the High-speed NT Link (1:N) Method (page 70).

4-1-1 Host Types and Settings

The types of host that can be connected to a PT by using the RS-232C ports of both Units, and the settings to be made at the host, are described here.

When Using the Host Link Method

Compatible Host Units

Some models and series of OMRON PLCs have the host link function built in.

In the CS/CJ-series or CQM1H PLCs, the host link method can be used by installing a Serial Communications Board/Unit. In addition, some C200HX/ HG/HE(-Z)E CPU Unit can be connected in the host link method by installing a Communications Board.

Check the model and series of the PLC, the type of installed Serial Communi- cations Board, Serial Communications Unit, or Host Link Unit before making a connection.

The hosts that can be connected to the NT631/NT631C by the host link method using the RS-232C ports of both Units are indicated in the table below.

PLC

Units with Built-in Host Link

CPU Units Connectable with

Host Link Unit or

Connect-

Series

Function

Host Link Units or Expansion

Communications

able to

 

 

Communications Board/Units

Board/Unit

 

 

 

 

 

 

CS Series

CS1G-CPU42/43/44/45-E(V1)

CS1G-CPU42/43/44/45-E(V1)

CS1W-SCU21(-V1)

CS1G

 

CS1H-CPU63/64/65/66/67-E(V1)

CS1H-CPU63/64/65/66/67-E(V1)

CS1W-SCB21(-V1)

CS1H

 

CS1G-CPU42H/43H/44H/45H

CS1G-CPU42H/43H/44H/45H

CS1W-SCB41(-V1)

CS1D

 

CS1H-CPU63H/64H/65H/66H/67H

CS1H-CPU63H/64H/65H/66H/67H

 

 

 

CS1D-CPU65H/67H

CS1D-CPU65H/67H(*1)

 

 

CJ Series

CJ1G-CPU44/45

CJ1G-CPU44/45

CJ1W-SCU21(-V1)

CJ1G

 

CJ1G-CPU42H/43H/44H/45H

CJ1G-CPU42H/43H/44H/45H

CJ1W-SCU41(-V1)

CJ1H

 

CJ1H-CPU65H/66H/67H

CJ1H-CPU65H/66H/67H

 

CJ1M

 

CJ1M-CPU11/12/13/22/23

CJ1M-CPU11/12/13/22/23

 

 

 

 

 

 

 