Image 11

6 – Wiring

1

DANGER! LETHAL HIGH VOLTAGE HAZARD!

All wiring should be performed by a qualified electrician in accordance with the warnings in this manual, all applicable electrical and safety codes, and good wiring practices. Incorrect wiring may damage the UPS system severely and cause serious personal injury and property damage. Read Section 2 – Important Safety Instructions before proceeding.

6-1 Wiring Warnings

De-energize all input and output power sources of the UPS system before installing cables or making electrical connections.

Use flexible cable of sufficient length to permit UPS system servicing. The maximum cable length is 10 m (32.8 ft).

Use ferrule caps to cover termination cables within mechanical lugs, or use compression lugs in order to prevent frayed ends from shorting on the UPS system terminal block.

Use cabling rated VW-1, FT-1 or better.

Use cable sleeves and connector clamps.

The neutral conductor must be the same size as the current conductors.

Tighten all field wiring terminal connections with a torque of at least 3.95 N·m (35 in·lb); a torque of 11.8 N·m (100 in·lb) is required for the “In”, “Out” and “Battery” bolt-screw terminals.

Confirm that all cables are marked correctly according to their purpose, polarity, phase and diameter.

If the UPS system’s input/output power source is wye-wye, then “Neutral” and “Ground” must not be re-bonded at the UPS.

If the input power source has VNG>0, install a grounded wye secondary isolation transformer with a properly bonded neutral to ground before the UPS system and input power source.

For equipment requiring a neutral connection to an IT power distribution system that requires neutral isolation upon disconnect, the disconnect device must be a four-pole device and must disconnect all line conductors and the neutral conductor. If a disconnect device interrupts the neutral conductor, it must simultaneously interrupt all line conductors.

Allow the batteries to charge uninterrupted for 24 hours after the initial wiring connection and UPS startup.

Observe proper polarity by connecting negative to negative, positive to positive and the center point of the battery string to the normal “N” terminal. Do not bond the battery’s “N” terminal to the AC power “Neutral” or “Ground” as damage may result. Failure to observe proper polarity will damage the UPS system and create a serious risk of personal injury and property damage.

Observe proper phase by connecting R to R, S to S, T to T and N to N. Source power phase rotation must be verified as RST before powering the UPS. Failure to observe proper phase will damage the UPS system and create a risk of personal injury and property damage.

6-2 Wiring Preparation

De-energize all input and output (AC and DC) of the UPS system and external battery cabinet (if present).

Mark all cables according to their correct purpose, polarity, phase and diameter.

Review the diagrams in Section 6-3and Section 6-4to familiarize yourself with the terminal blocks.

Consult the table in Section 6-5to find the correct electrical input/output characteristics for the UPS system.

Note: If the UPS system’s input/output power source is wye-wye, then “Neutral” and “Ground” must not be re-bonded at the UPS. If the input power source has VNG>0, install an isolation transformer as part of the UPS input power source and bond “Neutral” and “Ground” together at the isolation transformer’s output.

11

2

3

4

5

6

7

8

9

10

11

12

13

14

12-212-93-3141.indb 11

12/28/2012 11:17:22 AM

Page 11
Image 11
Tripp Lite SU120KX2 owner manual Wiring Preparation

SU120KX2 specifications

The Tripp Lite SU120KX2 is an advanced uninterruptible power supply (UPS) that provides reliable backup power and surge protection for critical devices. Engineered for small and medium-sized businesses, this UPS is ideal for safeguarding sensitive electronics such as servers, network devices, and telecommunications equipment.

One of the standout features of the SU120KX2 is its impressive 1200VA power capacity. This allows it to deliver significant run time during power outages, ensuring that your equipment remains operational until power is restored or until you can safely shut down your systems. With a pure sine wave output, this UPS simulates utility power, providing stable voltage and frequency to connected devices. This is particularly important for equipment that is sensitive to power fluctuations, as it helps to maintain optimal performance and longevity.

The SU120KX2 is equipped with multiple battery and surge protected outlets, providing flexibility for connecting various devices. It includes USB and serial connectivity options for easy communication with connected equipment, enabling monitoring of battery status and power conditions. An LCD screen provides real-time information on battery level, load capacity, and input/output voltage, ensuring users are informed about the status of their power supply.

Another notable feature is the built-in automatic voltage regulation (AVR). This technology helps to stabilize input voltage levels, correcting minor fluctuations without switching to the battery, thereby extending the life of the battery while ensuring your devices receive consistent and clean power. Furthermore, the SU120KX2 includes advanced battery management features that optimize battery performance and provide notifications for battery replacement when necessary.

For added convenience, the Tripp Lite SU120KX2 offers hot-swappable battery capabilities, allowing users to replace batteries without shutting down connected devices. This ensures that your critical operations are not interrupted, making it an ideal choice for businesses that cannot afford downtime.

Overall, the Tripp Lite SU120KX2 combines robust performance with reliable protection, making it a perfect solution for businesses looking to secure their electronic infrastructure against power disturbances. With its manageable size, advanced features, and user-friendly interface, the SU120KX2 stands out as a dependable UPS that meets the needs of various applications while ensuring the integrity and availability of your critical systems.