18 – Start-Up, Shutdown and Bypass (continued)

8-6 Shutdown Procedure (Single UPS—SUS)

Warning: The UPS system shutdown procedure will eliminate the AC power output for all loads. Before shutdown, confirm that all loads

2 are turned off or place the UPS system in manual bypass mode (See Section 8-5) to keep loads powered by the bypass power path.

3

4

5

6

7

If the UPS is in NORMAL mode (green LED ON, LCD displays “Load Protected-On Line Mode”), then you must stop the

inverter by pressing and holding the OFF button until the UPS beeps, then release the button. The UPS will transfer to Bypass.

Confirm the UPS is in BYPASS (amber Bypass LED is ON; LCD displays “Load Unprotected-On Auto Bypass”). Do not proceed if it is not on BYPASS.

Turn OFF the OUTPUT circuit breaker .

Turn OFF the MAIN INPUT circuit breaker .

Turn OFF the BYPASS UNIT circuit breaker .

Wait until the Power Module fans turn OFF and the LCD display goes blank (this may take a minute or two), then turn OFF the BATTERY BREAKER. The external battery cabinets will have the BATTERY BREAKER behind the front door/panel or elsewhere.

Note: If the UPS system remains off for an extended period of time, it should be turned on periodically to allow the batteries to recharge. The UPS system should be turned on and the batteries should be recharged at least one uninterrupted 24-hour period every 3 months. Failure to recharge the batteries periodically may cause irreversible battery damage.

8-7 Preliminary Checklist (Parallel UPS—MUS)

 

A

 

C

1

B

 

3

 

5

4

Q4

Q3

Q2

Q1

Output

Manual

Bypass

Main

2

Bypass

Input

Input

 

 

 

Position of circuit breaker switches shown as in manual bypass mode.

Warning: Parallel configurations of two, three or four UPS systems (for N+1 redundancy or capacity) are allowed. Do not attempt to link more than four UPS systems via parallel configuration. All UPS systems must have the same rating, kVA capacity and power module

8 level firmware version (See Section 10-6) for parallel UPS configuration. Attempting to link dissimilar UPS systems will damage the UPS systems and create a serious risk of personal injury and property damage.

9

10

11

12

13

14

All circuit breaker switches should be off, including the battery breakers of the external battery cabinets.

Confirm that no voltage potential exists between Neutral and Ground.

Confirm that the input power source matches the rating (voltage, frequency and phase) of the UPS systems.

Each UPS must have its parallel group set to 2 and a different “Parallel ID” that indicates the UPS systems are running in parallel. See Section 10-5-5for more details.

Note: After start-up, the UPS systems will perform a brief self-test and display the results on the LCD screen. After a successful self-test, the UPS systems will provide AC power to the connected equipment load.

24

12-212-93-3141.indb 24

12/28/2012 11:17:35 AM

Page 24
Image 24
Tripp Lite SU120KX2 owner manual Shutdown Procedure Single UPS-SUS, Preliminary Checklist Parallel UPS-MUS

SU120KX2 specifications

The Tripp Lite SU120KX2 is an advanced uninterruptible power supply (UPS) that provides reliable backup power and surge protection for critical devices. Engineered for small and medium-sized businesses, this UPS is ideal for safeguarding sensitive electronics such as servers, network devices, and telecommunications equipment.

One of the standout features of the SU120KX2 is its impressive 1200VA power capacity. This allows it to deliver significant run time during power outages, ensuring that your equipment remains operational until power is restored or until you can safely shut down your systems. With a pure sine wave output, this UPS simulates utility power, providing stable voltage and frequency to connected devices. This is particularly important for equipment that is sensitive to power fluctuations, as it helps to maintain optimal performance and longevity.

The SU120KX2 is equipped with multiple battery and surge protected outlets, providing flexibility for connecting various devices. It includes USB and serial connectivity options for easy communication with connected equipment, enabling monitoring of battery status and power conditions. An LCD screen provides real-time information on battery level, load capacity, and input/output voltage, ensuring users are informed about the status of their power supply.

Another notable feature is the built-in automatic voltage regulation (AVR). This technology helps to stabilize input voltage levels, correcting minor fluctuations without switching to the battery, thereby extending the life of the battery while ensuring your devices receive consistent and clean power. Furthermore, the SU120KX2 includes advanced battery management features that optimize battery performance and provide notifications for battery replacement when necessary.

For added convenience, the Tripp Lite SU120KX2 offers hot-swappable battery capabilities, allowing users to replace batteries without shutting down connected devices. This ensures that your critical operations are not interrupted, making it an ideal choice for businesses that cannot afford downtime.

Overall, the Tripp Lite SU120KX2 combines robust performance with reliable protection, making it a perfect solution for businesses looking to secure their electronic infrastructure against power disturbances. With its manageable size, advanced features, and user-friendly interface, the SU120KX2 stands out as a dependable UPS that meets the needs of various applications while ensuring the integrity and availability of your critical systems.