18 – Start-Up, Shutdown and Bypass (continued)

 

8-9 Shutdown Procedure (Parallel UPS—MUS)

2

Warning: The UPS system shutdown procedure will eliminate the AC power output for all loads. Before shutdown, confirm that all loads

are turned off or place the UPS systems in manual bypass mode (See Section 8-10) to keep loads powered by the bypass power path.

3

4

For the UPS system you wish to shut down, press the OFF button

for 3 seconds (until you hear a beep), then release the button. If the other UPS systems can support the connected equipment loads alone, the UPS system that was turned off will shut down its inverter and its LCD screens will read “LOAD NOT POWERED”. The other UPS system’s LCD screen will read “ONLINE MODE”. If the total connected equipment load is too large to be handled by the remaining UPS systems, all UPS systems will shut down their inverters and switch to bypass mode, and their LCD screens will read “ON AUTO BYPASS”.

 

B

1

A

 

 

 

 

Confirm the UPS you wish to shut down is in bypass mode (amber

5

 

 

bypass LED

 

 

is on, LCD displays “ON AUTO BYPASS”).

 

 

 

 

 

 

 

 

For the UPS system you wish to shut down, switch off the main

 

 

 

 

 

input circuit breaker switch

Q1

, then switch off the output circuit

 

 

 

breaker switch

 

 

.

 

 

 

 

 

Q4

 

 

 

 

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

For the UPS system you wish to shut down, switch off the bypass

 

 

 

 

 

 

7

 

 

 

input circuit breaker switch

Q2

.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

 

When the UPS system is completely shut down, the LCD screen

 

 

will be completely off. Wait until the power module fans power off

 

 

 

and the LCD display goes blank (this may take a minute or two).

 

 

 

Then, switch off the external battery cabinet circuit breaker switch

 

 

 

 

 

 

of each battery cabinet connected to the UPS you wish to shut

10

 

 

down.

 

 

 

 

 

 

Note: If the UPS system remains off for an extended period of time, it

 

 

should be turned on periodically to allow the batteries to recharge. The

 

 

UPS system should be turned on and the batteries should be recharged

11

 

at least one uninterrupted 24-hour period every 3 months. Failure

 

to recharge the batteries periodically may cause irreversible battery

damage.

Q4

 

 

Q1

Output

Manual

Bypass

Main

2

Bypass

Input

Input

 

 

 

 

 

Q2

 

Output

Manual

Bypass

Main

3

Bypass

Input

Input

 

 

 

4

12

13

14

26

12-212-93-3141.indb 26

12/28/2012 11:17:47 AM

Page 26
Image 26
Tripp Lite SU120KX2 owner manual Shutdown Procedure Parallel UPS-MUS, Damage

SU120KX2 specifications

The Tripp Lite SU120KX2 is an advanced uninterruptible power supply (UPS) that provides reliable backup power and surge protection for critical devices. Engineered for small and medium-sized businesses, this UPS is ideal for safeguarding sensitive electronics such as servers, network devices, and telecommunications equipment.

One of the standout features of the SU120KX2 is its impressive 1200VA power capacity. This allows it to deliver significant run time during power outages, ensuring that your equipment remains operational until power is restored or until you can safely shut down your systems. With a pure sine wave output, this UPS simulates utility power, providing stable voltage and frequency to connected devices. This is particularly important for equipment that is sensitive to power fluctuations, as it helps to maintain optimal performance and longevity.

The SU120KX2 is equipped with multiple battery and surge protected outlets, providing flexibility for connecting various devices. It includes USB and serial connectivity options for easy communication with connected equipment, enabling monitoring of battery status and power conditions. An LCD screen provides real-time information on battery level, load capacity, and input/output voltage, ensuring users are informed about the status of their power supply.

Another notable feature is the built-in automatic voltage regulation (AVR). This technology helps to stabilize input voltage levels, correcting minor fluctuations without switching to the battery, thereby extending the life of the battery while ensuring your devices receive consistent and clean power. Furthermore, the SU120KX2 includes advanced battery management features that optimize battery performance and provide notifications for battery replacement when necessary.

For added convenience, the Tripp Lite SU120KX2 offers hot-swappable battery capabilities, allowing users to replace batteries without shutting down connected devices. This ensures that your critical operations are not interrupted, making it an ideal choice for businesses that cannot afford downtime.

Overall, the Tripp Lite SU120KX2 combines robust performance with reliable protection, making it a perfect solution for businesses looking to secure their electronic infrastructure against power disturbances. With its manageable size, advanced features, and user-friendly interface, the SU120KX2 stands out as a dependable UPS that meets the needs of various applications while ensuring the integrity and availability of your critical systems.