Programming Console Function

Section 6-12

6-12-1 Usable Systems

The Programming Console function can be used with an NT631/NT631C con- nected to a PLC when using the communications method indicated below.

Communica-

Applicable PLCs

Connected Port

tions Method

 

 

 

 

 

 

NT Link (1:1)

C200HE-CPU42-(Z)E(*1)

CPU Unit’s built-in

 

 

C200HG-CPU43/63-(Z)E(*1)

RS-232C port

 

 

 

 

 

C200HX-CPU44/64-(Z)E(*1)

 

 

 

C200HX-CPU65-ZE(*1)

 

 

 

C200HX-CPU85-ZE(*1)

 

 

 

CPM2A-30CD@@-@(*1)

 

 

 

CPM2A-40CD@@-@(*1)

 

 

 

CPM2A-60CD@@-@(*1)

 

 

 

CPM2C-10@@@@@@-@(*2)

 

 

 

CPM2C-20@@@@@@-@(*2)

 

 

 

CQM1-CPU4@-EV1(*1)

 

 

 

CQM1H-CPU21/51/61(*1)

 

 

 

SRM1-C02-V2

 

 

 

 

 

 

 

CPM1-10CDR-@

Peripheral port (*3)

 

 

CPM1-20CDR-@

 

 

 

CPM1A-10CD@-@

 

 

 

CPM1A-20CD@-@

 

 

 

CPM1A-30CD@-@

 

 

 

CPM1A-40CD@-@

 

NT Link (1:N)

CS1G-CPU42/43/44/45-EV1

CPU Unit’s built-in

 

 

CS1H-CPU63/64/65/66/67-EV1

RS-232C port

 

 

 

 

 

CS1G-CPU42H/43H/44H/45H

Peripheral port (*4)

 

 

CS1H-CPU63H/64H/65H/66H/67H

 

 

 

CS1D-CPU66H/67H

 

 

 

CJ1G-CPU44/45

 

 

 

CJ1G-CPU42H/43H/44H/45H

 

 

 

CJ1H-CPU65H/66H/67H

 

 

 

CJ1M-CPU11/12/13/21/22/23

 

 

 

 

 

*1 The peripheral port Programming Console always has priority. If a Pro- gramming Console is connected later, the Programming Console function of the NT631/NT631C is invalidated and operation from the NT631/ NT631C becomes impossible.

*2 The CPM2C-CN111 Connecting Cable splits the PLC’s Communications Port into a RS-232C port and a peripheral port.

*3 An RS-232C cable cannot be connected to the peripheral port. An RS- 232C adapter (CPM1-CIF01) is required.

*4 The RS-232C cable cannot be directly connected to the peripheral port. An RS-232C converting cable (CS1W-CN118) is required.

Reference: Note that the Programming Console function cannot be used with CPM1, CQM1, and C200HX/HG/HE(-Z)E PLCs of the following lot numbers.

CPM1: @@@5, @@*6

where * is a number in the range 1 to 9 or the letter X or Y.

215

Page 232
Image 232
Omron NT631C manual Usable Systems, Communica Applicable PLCs Connected Port Tions Method