Connecting to the RS-232C Port at the Host

Section 4-1

 

 

 

 

 

Word #

Writing Value

Settings

 

 

 

 

 

DM6556

0303

Data length 7 bits, 2 stop bits, even parity, communica-

 

 

 

tions speed: 9600 bps

 

 

 

 

 

 

0304

Data length 7 bits, 2 stop bits, even parity, communica-

 

 

 

tions speed: 19200 bps

 

 

 

 

 

DM6558

0000

Unit # 00

 

 

 

 

 

When using port B of the Communications Board of C200HX/HG/HE(-Z)E

 

 

 

 

 

Word #

Writing Value

Settings

 

 

 

 

 

DM6550

0001

Host link mode, no CTS control

 

 

 

Communications conditions set by the contents of DM

 

 

 

 

 

DM6551

0303

Data length 7 bits, 2 stop bits, even parity, communica-

 

 

 

tions speed: 9600 bps

 

 

 

 

 

 

0304

Data length 7 bits, 2 stop bits, even parity, communica-

 

 

 

tions speed: 19200 bps

 

 

 

 

 

DM6553

0000

Unit # 00

 

 

 

 

 

When using a CPM1

 

 

 

 

 

 

Word #

Writing Value

Settings

 

 

 

 

 

DM6650

0001

Host link mode

 

 

 

Communications conditions set by the contents of DM

 

 

 

 

 

DM6651

0303

Data length 7 bits, 2 stop bits, even parity, communica-

 

 

 

tions speed: 9600 bps

 

 

 

 

 

 

0304

Data length 7 bits, 2 stop bits, even parity, communica-

 

 

 

tions speed: 19200 bps

 

 

 

 

 

DM6653

0000

Unit # 00

 

 

 

 

Connecting to a CPM2C

The CPM2C PLCs do not have the same kind of port connectors found on CS/ CJ-series PLCs. The CPM2C’s communications port handles both RS-232C and peripheral port connections which are divided internally. Therefore, when using the CPM2C, it is necessary to select RS-232C or peripheral port con- nections, according to the kind of cable and port (on the cable) used, as shown in the following table. Refer to the CPM2C Operation Manual for more details.

Port connecting to PT

 

PLC Setup

 

 

RS-232C port (D-Sub 9-pin) of CPM2C-CN111

Built-in RS-232C port settings

 

 

Peripheral port of CPM2C-CN111

Peripheral port settings

 

 

RS-232C port (D-Sub 9-pin) of CS1W-CN118

Built-in RS-232C port settings

 

 

Peripheral port of CS1W-CN114

Peripheral port settings

 

 

 

 

Peripheral port

 

 

 

CPM2C-CN111CPM2CCS1W-CN118CPM2C

CS1W-CN114 CPM2C

RS-232C port

RS-232C port

 

Peripheral port

(D-Sub 9-pin, female)

 

 

(D-Sub 9-pin, female)

Setting the DIP Switches of a C200HX/HG/HE(-Z)E, CQM1 or CQM1H

When using a C200HX/HG/HE(-Z)E, CQM1, or CQM1H the DIP switches on the front panel must be set as shown below in order to make the settings in the PLC Setup area (data memory) effective.

57

Page 74
Image 74