Troubleshooting

 

Section 7-1

 

 

 

NT631/NT631C

Cause

Remedy

Symptoms

 

 

The graph display does not

One of the percentage display set-

Set the 100%, 0%, and 100% values in the following

change.

tings — 100%, 0%, or 100% — is

relationship:

 

incorrect.

100% value < 0% value < 100% value

 

 

 

The trend graph display

The cycle for graph display update

Delete other elements on the same screen as the

does not agree with the

processing is longer than the set

trend graph that are allocated to the host and have a

actual time axis.

sampling cycle.

high update frequency. Or lengthen the sampling

 

 

cycle.

 

 

 

The Programming Console

The communications settings are

Set the communications method as follows when

function cannot be used.

incorrect.

using the Programming Console function.

 

 

• With C-series PLC: 1:1 NT Link

 

 

• With CS/CJ-series PLC:

 

 

1:N NT Link (standard or high-speed)

 

 

 

 

A Programming Console is con-

It is not possible to use a Programming Console and

 

nected.

the Programming Console function at the same time.

 

 

Disconnect the Programming Console.

 

 

 

 

The PLC does not support the Pro-

Not all PLCs support the Programming Console func-

 

gramming Console function.

tion. Check the model of PLC you are using. (6-12

 

 

Programming Console Function)

 

 

 

 

The system program for other ven-

The Programming Console function can be used only

 

dor’s PLCs has been installed. (PLC

when the system program for OMRON PLCs is

 

models other than OMRON.)

installed. Install the correct system program.

 

 

 

The Device Monitor func-

The communications settings are not

Set the communications method as follows when

tion cannot be used.

correct.

using the Device Monitor function.

 

 

• With C-series PLCs: 1:1 NT Link or 1:N NT Link

 

 

• With CS/CJ-series PLCs:

 

 

1:N NT Link (standard or high-speed)

 

 

 

 

The PLC does not support the Device

Not all PLCs support the Device Monitor function.

 

Monitor function.

Check the model of PLC you are using. Refer to 6-13

 

 

Device Monitor Function for details.

 

 

 

 

The system program installed in the

The Device Monitor function can be used only when

 

PT is for a PLC maker other than

the PT is connected to a PT with the system program

 

OMRON.

for OMRON PLCs installed. Install a system program

 

 

that supports the Device Monitor function.

 

 

 

The memory table display

Since the memory table is allocated

When the contents of the memory table are set as a

contents differ from the ini-

to the host memory, the display is

fixed value, do not allocate the memory table to the

tial value set at the Sup-

updated in accordance with the con-

host.

port Tool.

tents of the host memory.

 

 

 

 

 

The battery voltage has dropped and

Replace the battery and execute memory table initial-

 

the data in the memory table has

ization. (7-3-1 Replacing the Battery, page 241, and

 

been destroyed.

6-4-5 Initializing the Memory Tables, page 141)

 

 

 

 

Since ON is set for the resume func-

Execute memory table initialization. (6-4-5 Initializing

 

tion, the initial values of the screen

the Memory Tables, page 141)

 

data memory are not written to the

If the resume function does not need to be used, use

 

memory tables.

 

the NT631/NT631C with the resume function OFF.

 

 

 

 

(6-9-10 Setting the Resume Function, page 177)

 

 

 

 

The numeral memory table is speci-

Calculations are executed continuously while the PT

 

fied as the destination for a mathe-

is operating and the calculation results are automati-

 

matical table’s results.

cally written to the memory table. Specify another

 

 

numeral memory table or a word in the host.

 

 

 