Various System Settings

Section 6-9

To confirm the settings and quit the memory switch setting screen, press the Quit touch switch. The settings made last will be set and the NT631/ NT631C will return to the MAINTENANCE MODE MENU screen.

To quit the memory switch setting screen without confirming the settings, press the Abort touch switch. The NT631/NT631C will return to the MAIN- TENANCE MODE MENU screen with the previous settings still in effect.

6-9-13 Setting the Retry Count

The NT631/NT631C does not immediately display an error screen when a communications error occurs, but tries to re-establish communications. The Retry Counts setting specifies the number of attempts to be made to re-estab- lish communications. If communications cannot be recovered within this num- ber of attempts, the following happens depending on the setting made for the Comm. Auto-return memory switch (page 179).

Comm. Auto-return ON:

Operation in the RUN mode is continued without displaying an error screen. Regardless of the setting made for Retry Counts, attempts to re-establish communications are repeated until normal communications are achieved.

Comm. Auto-return OFF:

The RUN mode is ended and an error screen is displayed. On pressing the OK touch switch on the error screen, the screen displayed immediately before is redisplayed and attempts are made to re-establish communications.

The System Menu can be displayed from the error screen by pressing any two of the four corners of the touch panel simultaneously.

The setting range is 0 to 255 times. The default (factory) setting is 5 times.

Reference: For details on communications errors, refer to 7-2-5 Communications Errors and Their Remedies (page 233).

182

Page 199
Image 199
Omron NT631C manual Setting the Retry Count, Comm. Auto-return on, Comm. Auto-return OFF